Plan Review Notes
Plan Review Notes For Permit 08080195
Permit Number 08080195
Review Stop M
Sequence Number 1
Notes
Date Text
2008-08-26 10:59:14REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M1.0: VENTILATION CALCULATIONS STATE THEY ARE
 BASED ON ASHRAE 62.1-2007. HOWEVER, THE REFERENCED
 STANDARD IS CURRENTLY ASHRAE 62.1-2004 EDITION IN
 ACCORDANCE WITH FBCM CHAPTER 15. PLEASE REFERENCE THE
 CORRECT STANDARD ON THE PLANS AT THE VENTILATION
 CALCULATIONS TABLE.
  
 2. PAGE M1.0: THE DINING AREA DEFAULT OCCUPANT DENSITY
 BASED ON TABLE 6-1 FOR DINING ROOMS IS 70/1000 SQ. FT.
 WITH THE GIVEN SQUARE FOOTAGE OF 1800, THIS GIVES A
 DEFAULT OCCUPANT LOAD OF 126 PERSONS. BASED ON EQUATION
 6-1, THE TOTAL OUTSIDE AIR REQUIRED FOR THE DINING
 AREAS IS 1269 CFM. PLEASE ADJUST OUTDOOR AIR QUANTITIES
 ACCORDINGLY.
  
 3. PAGE M1.0: NOTE #1, WHICH REFERENCED
 13-409.1.ABC.3.3 FOR SHUTOFF DAMPER CONTROLS, CALLS FOR
 MOTORIZED DAMPER ON THE OA INTAKE FOR AHU #1 WITH NO
 PROVISIONS FOR AHU #2 OR AHU #3. EVEN THOUGH THEY SHOW
 LESS THAN 300 CFM, A BACK DRAFT DAMPER, AT A MINIMUM,
 IS REQUIRED TO MEET THE REQUIREMENTS OF THIS CODE
 SECTION.
 NOTE: BASED ON COMMENT #2, THE OUTSIDE AIR VOLUME FOR
 EACH UNIT IS LIKELY TO BE OVER 300 CFM AND THEREFORE A
 MOTORIZED DAMPER WILL BE REQUIRED.
  
 4. PAGE M2.0: DIFFUSER AND FLEXIBLE DUCT DETAILS ARE
 NOT CODE COMPLIANT. THE MINIMUM WIDTH OF HANGERS AND
 SUPPORTS FOR FLEXIBLE DUCTS SHALL BE 1.5 INCHES AND THE
 MAXIMUM SAG BETWEEN SUPPORTS SHALL BE 1/2 INCH PER FOOT
 IN ACCORDANCE WITH FBCM 603.5.6.6. ADJUST DETAILS TO
 SHOW COMPLIANCE WITH THIS SECTION.
  
 NOTE: THE METHOD A ENERGY CALCULATIONS WHICH WERE
 SUBMITTED WITH THIS APPLICATION WERE NOT REVIEWED FOR
 COMPLIANCE WITH THE MECHANICAL PROVISIONS OF FBCB
 CHAPTER 13. METHOD A CALCULATIONS ARE NEITHER
 APPROPRIATE NOR REQUIRED FOR THIS PROJECT AS THIS IS
 NOT A WHOLE BUILDING AND DOES NOT QUALIFY AS A
 RENOVATION AS DEFINED IN FBCB SECTION 13-202. THE
 MINIMUM REQUIRED FOR COMPLIANCE WITH FBCB CHAPTER 13
 FOR THIS PROJECT CAN BE FOUND IN SECTION 13-101.6 AND
 ARE AS FOLLOWS:
  
 THERMAL EFFICIENCY STANDARDS ARE SET FOR THE FOLLOWING
 BUILDING SYSTEMS WHERE NEW PRODUCTS ARE INSTALLED OR
 REPLACED IN EXISTING BUILDINGS, AND FOR WHICH A PERMIT
 MUST BE OBTAINED. SUCH SYSTEMS SHALL MEET THE MINIMUM
 EFFICIENCIES ALLOWED FOR THAT SYSTEM ON FORM 400C FOR
 COMMERCIAL BUILDINGS AND ON FORM 600C FOR RESIDENTIAL
 BUILDINGS.
 1. HEATING, VENTILATING OR AIR CONDITIONING SYSTEMS;
 2. SERVICE WATER OR POOL HEATING SYSTEMS;
 3. ELECTRICAL SYSTEMS AND MOTORS;
 4. LIGHTING SYSTEMS.
  
 THESE REQUIREMENTS HAVE BEEN DEMONSTRATED ON THE PLANS
 FOR THE NEWLY INSTALLED MECHANICAL SYSTEMS. PLEASE SEE
 OTHER TRADE REVIEWS FOR COMMENTS REGRADING OTHER
 AFFECTED SYSTEMS.
  
 NOTE: NO INFORMATION WAS PROVIDED ON THESE PLANS
 REGARDING KITCHEN HOOD/EXHAUST AND WALK-IN COOLER
 SYSTEMS. SEPARATE PERMITS AND PLANS ARE REQUIRED FOR
 THESE SYSTEMS.
  