Notes
Date Text
2008-09-05 15:26:55*****DENIED*****
  
 1. ON SHEET A2.2, SHOW THE PATH OF EGRESS FROM THE OPEN
 KITCHEN AREA (ROOM 113) .
  
 2. EXIT LIGHTS ARE SHOWN ON BOTH SIDES OF DOOR #6
 LOCATED BETWEEN COORIDOR 111 AND 112. THIS WOULD APPEAR
 TO BE CONFLICT OF EGRESS USAGE.
  
 3. ON SHEET A3.0 AND E2.0 IN THE CEILING LEGEND,
 REFERENCE IS MADE TO THE ENGINEERED FIRE SPRINKLER
 DRAWINGS COMPLING WITH NFPA 96. PLEASE BE ADVISED THAT
 NFPA 96 IS THE STANDARD FOR VENTILATION CONTROL AND
 FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS.
  
 4. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THIS
 SCOPE OF WORK. THESE DEVICES MAY BE SHOWN ON SHEET E1.0
 (POWER PLAN) .
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  