| Plan Review Notes For Permit 08080195 |
| Permit Number |
08080195 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-09-05 15:26:55 | *****DENIED***** | | | | | | 1. ON SHEET A2.2, SHOW THE PATH OF EGRESS FROM THE OPEN | | | KITCHEN AREA (ROOM 113) . | | | | | | 2. EXIT LIGHTS ARE SHOWN ON BOTH SIDES OF DOOR #6 | | | LOCATED BETWEEN COORIDOR 111 AND 112. THIS WOULD APPEAR | | | TO BE CONFLICT OF EGRESS USAGE. | | | | | | 3. ON SHEET A3.0 AND E2.0 IN THE CEILING LEGEND, | | | REFERENCE IS MADE TO THE ENGINEERED FIRE SPRINKLER | | | DRAWINGS COMPLING WITH NFPA 96. PLEASE BE ADVISED THAT | | | NFPA 96 IS THE STANDARD FOR VENTILATION CONTROL AND | | | FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS. | | | | | | 4. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THIS | | | SCOPE OF WORK. THESE DEVICES MAY BE SHOWN ON SHEET E1.0 | | | (POWER PLAN) . | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|