Plan Review Notes
Plan Review Notes For Permit 08080195
Permit Number 08080195
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-28 14:09:52** DENIED PLAN **
  
  
  
 1) NOTE:PLEASE SEE THE SUBMITTED METHOD *A*
 CALCULATIONS MAY NOTBE USED. THIS IS NOT A WHOLE
 BUILDING. PLEASE SEE 13-101.1
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS AND
 INDICATE THE METHOD TO BE USED. THE PLANS MENTION WHOLE
 AREA HOWEVER BASED ON OCCUPANCY TYPE PER 13-415.2.C THE
 LEVELS OF LIGHTING SHOWN ON PLANS EXCEED THAT PERMITTED
 BY TABLE C.
 PLEASE SEE 13-415.2.ABC.1.1,.1.2 AND .1.3
 PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND. THE
 LEGEND MUST BE COMPLETE AT THIS TIME TO FIGURE CORRECT
 WATTAGE ALLOWANCES. PLEASE KNOW THE WATTAGE WHICH MUST
 BE USED IS THE MAXIMUM VA OF THE FIXTURE, BALLAST OR
 TRANSFORMER NOT THE BULB. THE WATTAGE FOR TRACK
 LIGHTING SHALL BE WHICH EVER IS GREATER.
  
 2) NOTE: PLEASE COMPLETE THE PLANS FOR THE LIGHTING
 CONTROL SYSTEM AS NOTED.PLANS DO NOT SHOW ANY
 LOCATIONS FOR LIGHTING CONTROLS.
 THERE IS NOT ENOUGH INFORMATION ON PLANS AT THIS TIME.
 PLEASE PROVIDE ESTIMATED SCHEDULING. PLEASE PROVIDE ALL
 LOCATIONS OF CONTROLS, OVER RIDES AND ZONES. PLEASE BE
 SURE TO STATE ALL MAXIMUM OVER RIDE TIMES AS WELL AS
 MAXIMUM TIMES ON ANY OTHER DEVICES. PLEASE SEE SECTION
 BELOW FOR REQUIRED SEPARATE CONTROLS FOR DISPLAY/ACCENT
 LIGHTING.
 13-415.1.ABC.1.1,.1.2, .1.3 AND ANY EXTERIOR LIGHTING
 SHALL FALL UNDER .1.4.
  
 3) NOTE: PLEASE INDICATE THE TRACK LIGHTING LOADS PER
 220.43.
  
 4) NOTE: PLEASE ALSO SEE THE SUBMITTED ENERGY
 CALCULATIONS ARE PHOTO-COPIES AND ARE NOT ORIGINAL FAC
 61G15-23.002, FS 471.025
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved