Plan Review Notes
Plan Review Notes For Permit 08080193
Permit Number 08080193
Review Stop P
Sequence Number 2
Notes
Date Text
2008-10-03 15:37:45DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. SUBMIT A FLOOR PLAN FOR THE SECOND FLOOR SHOW ALL
 REQUIRED MINIMUM FACILITIES PER TABLES 1004.1.2 & 403.1
 AS WELL AS ALL THE SEATING TO VERIFY THE SEATING COUNT
 INDICATED ON SHT C-2. SECTION 106.1.2.
 ****RESPONSE NOTED, BUT THE SEATING SHALL BE SHOWN TO
 VERIFY MINIMUM FACILITIES REQUIRED BY TABLE 403.1.
  
 2. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM AND A
 WATER ISOMETRIC RISER DIAGRAM PER SECTION 106.3.5.1.3.
 SHOW ALL THE PIPE SIZES, CLEANOUTS, TRAPS AND VENTS FOR
 THE SANITARY RISER, AND SHOW ALL PIPE SIZES, VALVES
 AND, (WHERE REQUIRED BY SECTION 604.9), WATER HAMMER
 ARRESTORS. SECTIONS 704, 706, 708, 710, 604, 606 &
 607.
 ****RESPONSE NOTED, BUT THE RISER DIAGRAM SHOWS THE
 BUILDING DRAIN CAPPED OFF UPSTREAM OF THE HAND SINK AND
 FLOOR SINK. PLEASE INDICATE WHERE THE TOILET ROOMS AND
 ANY OTHER FIXTURE ON THE 2ND FLOOR CONNECT TO THE
 BUILDING SEWER. SECTIONS 106.1.1 &301.3.
  
 3. SHT 1.0A WITH THE STATE OF FLORIDA DBPR STAMP SHALL
 BE SIGNED, SEALED AND DATED AS REQUIRED IN SECTION
 106.1, FAC 61G15-23.002(1), 61G1-16.001, FS 471.025 &
 481.2055.
 ****RESPONSE NOTED, BUT THE SHEET WITH THE DBPR STAMP
 IS NOT SIGNED AND SEALED IN ONE SET AND HAS BEEN
 DELETED IN THE OTHER SET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]