Plan Review Notes
Plan Review Notes For Permit 08080193
Permit Number 08080193
Review Stop E
Sequence Number 2
Notes
Date Text
2008-10-21 14:44:02 
 ** DENIED 2ND REVIEW**
  
  
  
  
 1) NOTE: PLANS NOW INDICATE RE-USE OF EXISTING
 OCCUPANCY SENSOR HOWEVER HOW IS THIS POSSIBLE WHEN THIS
 AREA IS NEW?
 THESE ARE NEW DEVICES AND NOT ALL FIXTURES ARE EXISTS?
 LABEL NEW DEVICE TO BE INSTALLED.
 LABEL NEW FIXTURES.
 13-415.1.ABC.1.1, .1.2, 13-415.2, ETC
  
 2) NOTE: AS THE SECOND FLOOR IS NOW BECOMING THE PLACE
 OF USE FOR BATHROOMS ETC WE STILL NEED TO SEE THIS AREA
 AS MEETING CODE FOR LIFE SAFETY ETC. NO PLANS WERE
 SUBMITTED SHOWING NEW OR EXISTING CONDITIONS.
 A SITE VISIT TO SEE EXISTING CONDITIONS MAY BE
 REQUIRED.
 RESPONSE LETTER MENTIONS TO SEE REVISED PLANS HOWEVER
 ONLY PART OF THE ONE E-SHEET WAS REVISED.
 NFPA-101 7.8,7.9, NEC 2005, FBC 13-415.1, .2
 FBC 106.1.1 FOR COORDINATION, INFORMATION AND CLARITY
 OF PLANS/SCOPE.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  