| Date |
Text |
| 2008-10-21 14:44:02 | |
| | ** DENIED 2ND REVIEW** |
| | |
| | |
| | |
| | |
| | 1) NOTE: PLANS NOW INDICATE RE-USE OF EXISTING |
| | OCCUPANCY SENSOR HOWEVER HOW IS THIS POSSIBLE WHEN THIS |
| | AREA IS NEW? |
| | THESE ARE NEW DEVICES AND NOT ALL FIXTURES ARE EXISTS? |
| | LABEL NEW DEVICE TO BE INSTALLED. |
| | LABEL NEW FIXTURES. |
| | 13-415.1.ABC.1.1, .1.2, 13-415.2, ETC |
| | |
| | 2) NOTE: AS THE SECOND FLOOR IS NOW BECOMING THE PLACE |
| | OF USE FOR BATHROOMS ETC WE STILL NEED TO SEE THIS AREA |
| | AS MEETING CODE FOR LIFE SAFETY ETC. NO PLANS WERE |
| | SUBMITTED SHOWING NEW OR EXISTING CONDITIONS. |
| | A SITE VISIT TO SEE EXISTING CONDITIONS MAY BE |
| | REQUIRED. |
| | RESPONSE LETTER MENTIONS TO SEE REVISED PLANS HOWEVER |
| | ONLY PART OF THE ONE E-SHEET WAS REVISED. |
| | NFPA-101 7.8,7.9, NEC 2005, FBC 13-415.1, .2 |
| | FBC 106.1.1 FOR COORDINATION, INFORMATION AND CLARITY |
| | OF PLANS/SCOPE. |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |