| 2008-08-13 06:54:53 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SUBMIT A FLOOR PLAN FOR THE SECOND FLOOR SHOW ALL |
| | REQUIRED MINIMUM FACILITIES PER TABLES 1004.1.2 & 403.1 |
| | AS WELL AS ALL THE SEATING TO VERIFY THE SEATING COUNT |
| | INDICATED ON SHT C-2. SECTION 106.1.2. |
| | |
| | 2. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM AND A |
| | WATER ISOMETRIC RISER DIAGRAM PER SECTION 106.3.5.1.3. |
| | SHOW ALL THE PIPE SIZES, CLEANOUTS, TRAPS AND VENTS FOR |
| | THE SANITARY RISER, AND SHOW ALL PIPE SIZES, VALVES |
| | AND, (WHERE REQUIRED BY SECTION 604.9), WATER HAMMER |
| | ARRESTORS. SECTIONS 704, 706, 708, 710, 604, 606 & |
| | 607. |
| | |
| | 3. SHT 1.0A WITH THE STATE OF FLORIDA DBPR STAMP SHALL |
| | BE SIGNED, SEALED AND DATED AS REQUIRED IN SECTION |
| | 106.1, FAC 61G15-23.002(1), 61G1-16.001, FS 471.025 & |
| | 481.2055. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |