Plan Review Notes
Plan Review Notes For Permit 08080193
Permit Number 08080193
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-09-09 15:10:36***DENIED***
  
 1) ILLUSTRATE ADDRESS ON SHEET 1.1A, NEW OR EXISTING
 THAT SHALL BE MINIMUM 6" IN HEIGHT, 1" WIDTH AND
 CONTRASTING WITH THE BACKGROUND.
  
 2) ARE ANY DOORS PROVIDED WITH PANIC OR FIRE EXIT
 HARDWARE? NFPA 101, 2003 REQUIRES PANIC OR FIRE EXIT
 HARDWARE ON EXIT DOORS SERVING AN OCCUPANT LOAD OF 100
 OR MORE.
  
 3) ADDRESS TO BE DISPLAYED ON EACH SHEET SUBMITTED FOR
 REVIEW.
  
 4) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 5) SCOPE OF WORK INDICATES SECOND FLOOR WORK. SUBMIT
 ALL APPROPRIATE SHEETS FOR REVIEW.
  
 6) ILLUSTRATE LOCATION OF REQUIRED 2A-10B,C RATED FIRE
 EXTINGUISHERS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756