| Plan Review Notes For Permit 08080193 |
| Permit Number |
08080193 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-09-09 15:10:36 | ***DENIED*** | | | | | | 1) ILLUSTRATE ADDRESS ON SHEET 1.1A, NEW OR EXISTING | | | THAT SHALL BE MINIMUM 6" IN HEIGHT, 1" WIDTH AND | | | CONTRASTING WITH THE BACKGROUND. | | | | | | 2) ARE ANY DOORS PROVIDED WITH PANIC OR FIRE EXIT | | | HARDWARE? NFPA 101, 2003 REQUIRES PANIC OR FIRE EXIT | | | HARDWARE ON EXIT DOORS SERVING AN OCCUPANT LOAD OF 100 | | | OR MORE. | | | | | | 3) ADDRESS TO BE DISPLAYED ON EACH SHEET SUBMITTED FOR | | | REVIEW. | | | | | | 4) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILING. | | | | | | 5) SCOPE OF WORK INDICATES SECOND FLOOR WORK. SUBMIT | | | ALL APPROPRIATE SHEETS FOR REVIEW. | | | | | | 6) ILLUSTRATE LOCATION OF REQUIRED 2A-10B,C RATED FIRE | | | EXTINGUISHERS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|