| Notes |
| Date |
Text |
| 2008-08-28 08:21:31 | PLAN HAS NOTE INDICATING THE FIRE RATED CEILING IS TO | | | BE INSTALLED ABOVE ALL GRILLS AND DUCTS DIRECTLY BELOW | | | THE 2ND FLOOR DECK. IT IS NOT CLEAR ON PLANS WHETHER | | | THIS WILL ELIMINATE ALL DUCT PENETRATIONS OF THE RATED | | | CEILING ASSEMBLY. ALL PENETRATIONS OF RATED HORIZONTAL | | | ASSEMBLIES SHALL BE PROTECTED IN ACCORDANCE WITH FBCM | | | 607.6. ALL FIRE DAMPERS AND/OR CEILING DAMPERS SHALL BE | | | SHOWN ON PLANS IN ACORDANCE WITH FBCM 607.8. THIS WILL | | | BE VERIFIED IN THE FIELD BY THE INSPECTOR. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|