Plan Review Notes
Plan Review Notes For Permit 08080123
Permit Number 08080123
Review Stop B
Sequence Number 1
Notes
Date Text
2008-08-26 13:08:32BUILDING PLAN REVIEW
 PERMIT: 08080123
 ADD: 605 N OLIVE AVE
 CONT: ACOUSTI ENGINEERING
 TEL: (561)718-8134
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B)) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS AND
 THE 2004 EXISTING BUILDING CODE WITH ASSOCIATED
 SUPPLEMENTS.
  
 2)2004 EXISTING BUILDING CODE SECTION 301.5 THE
 DESIGN PROFESSIONAL OR AN OWNER MUST ELECT TO CHOISE TO
 WHAT LEVEL OF ALTERATION THEY WISH TO COMPLETE UNDER
 THIS PERMIT.
  
 3) PLANS STATE THAT THIS IS A REMOVAL OF THE EXISTING
 ACOUSTICAL CEILING GRID AND TILE AND REPLACEMENT WITH A
 FIRE RATED PRODUCT. ON THE UL SHEET THE SYSTEM
 A202(246-2) IS CIRCLED INDICATING WHICH PRODUCT ISTO BE
 USED. WHAT THE CHART DOES NOT PROVIDE IS THE GAUGE OF
 THE HANGER WIRE NOR THE FREQUENCY REQUIRED. THE PLANS
 ALSO FAIL TO PROVIDE WHAT TYPE OF FASTENER WILL BE USED
 TO FASTEN THE HANGER WIRE TO, TO SUPPORT THE CEILING
 GRID AND TILE. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
  
 4) BOTH LIGHT FIXTURES AND A/C GRILLES WILL BE
 PENETRATING THE FIRE RATED CEILING, PLEASE PROVIDE HOW
 COMPLIANCE WITH 712.4.1.1 AND 712.4.1.2 . WILL THE
 VARIOUS LIGHT FIXTURES HAVEFIRE RATINGS OR WILL THERE
 NEED TO HAVE FIRE RATED ASSEMBLIES AROUND THE FIXTURES
 ?
  
 5)THE UL SHEET PROVIDED INDICATES A 5/8 INCH CEILING
 PANEL BUT NO MENTION OF THE WEIGHT OF THE PANEL, PLEASE
 SHOW COMPLIANCE WITH 711.3.1, RESISTANCE TO UPWARD
 FORCES.
  
 6) PLEASE PROVIDE IF ACCESS DOORS WILL BE REQUIRED AS
 IN 711.3.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.