| 2008-08-26 13:08:32 | BUILDING PLAN REVIEW |
| | PERMIT: 08080123 |
| | ADD: 605 N OLIVE AVE |
| | CONT: ACOUSTI ENGINEERING |
| | TEL: (561)718-8134 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B)) INFORMATIONAL FL S S 713.13NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1C)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS AND |
| | THE 2004 EXISTING BUILDING CODE WITH ASSOCIATED |
| | SUPPLEMENTS. |
| | |
| | 2)2004 EXISTING BUILDING CODE SECTION 301.5 THE |
| | DESIGN PROFESSIONAL OR AN OWNER MUST ELECT TO CHOISE TO |
| | WHAT LEVEL OF ALTERATION THEY WISH TO COMPLETE UNDER |
| | THIS PERMIT. |
| | |
| | 3) PLANS STATE THAT THIS IS A REMOVAL OF THE EXISTING |
| | ACOUSTICAL CEILING GRID AND TILE AND REPLACEMENT WITH A |
| | FIRE RATED PRODUCT. ON THE UL SHEET THE SYSTEM |
| | A202(246-2) IS CIRCLED INDICATING WHICH PRODUCT ISTO BE |
| | USED. WHAT THE CHART DOES NOT PROVIDE IS THE GAUGE OF |
| | THE HANGER WIRE NOR THE FREQUENCY REQUIRED. THE PLANS |
| | ALSO FAIL TO PROVIDE WHAT TYPE OF FASTENER WILL BE USED |
| | TO FASTEN THE HANGER WIRE TO, TO SUPPORT THE CEILING |
| | GRID AND TILE. 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | |
| | 4) BOTH LIGHT FIXTURES AND A/C GRILLES WILL BE |
| | PENETRATING THE FIRE RATED CEILING, PLEASE PROVIDE HOW |
| | COMPLIANCE WITH 712.4.1.1 AND 712.4.1.2 . WILL THE |
| | VARIOUS LIGHT FIXTURES HAVEFIRE RATINGS OR WILL THERE |
| | NEED TO HAVE FIRE RATED ASSEMBLIES AROUND THE FIXTURES |
| | ? |
| | |
| | 5)THE UL SHEET PROVIDED INDICATES A 5/8 INCH CEILING |
| | PANEL BUT NO MENTION OF THE WEIGHT OF THE PANEL, PLEASE |
| | SHOW COMPLIANCE WITH 711.3.1, RESISTANCE TO UPWARD |
| | FORCES. |
| | |
| | 6) PLEASE PROVIDE IF ACCESS DOORS WILL BE REQUIRED AS |
| | IN 711.3.2. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |