| 2008-09-08 10:43:53 | |
| | |
| | |
| | |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3. PLEASE SEE NOTES ON PREVIOUS REVIEW WHICH |
| | REQUESTED TO INDICATE THE MINIMUM LIGHTING CONTROLS AS |
| | REQUIRED MEETING CODE. |
| | THE RESPONSE LETTER MENTIONS CONTROLS CHANGED TO |
| | *PHOTOCELL*. PHOTOCELL CONTROLS ARE FOR EXTERIOR |
| | LIGHTING MEASURING THE SUNLIGHT LEVELS. |
| | OCCUPANCY SENSORS ARE DEVICES FOR INTERIOR LIGHTING |
| | CONTROLS IN EITHER CASE THE PLANS STILL INDICATE |
| | STANDARD SINGLE POLE SWITCHES WHICH ARE NOT PERMITTED. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES WITH RESPECT |
| | TO THE LIGHTING PERFORMANCE CALCULATIONS REQUIRED. |
| | RESPONSE MENTIONS THESE WERE DONE AND ON PLANS. HOWEVER |
| | THE PLANS DO NOT INDICATE ANY LIGHTING PERFORMANCE |
| | CALCULATIONS.13-415.2.ABC.1.1, .1.2 |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH |
| | RESPECT TO SIGN CIRCUIT REQUIRED LOCATION. THE PREVIOUS |
| | COMMENT MENTIONED THE PANEL SCHEDULE DID INDICATE THE |
| | EXISTING 240V CIRCUIT HOWEVER TO PLEASE INDICATE THE |
| | LOCATION SO THAT VERIFICATION OF 600.5 CAN BE MADE. THE |
| | RESPONSE MENTIONS THIS WAS DONE HOWEVER THE PLANS DO |
| | NOT SHOW ANY EXISTING OR NEW SIGN CIRCUITS ON PLANS AT |
| | LOCATIONS REQUIRED PER 600.5. |
| | |
| | 4) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS |
| | ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |