Plan Review Notes
Plan Review Notes For Permit 08080113
Permit Number 08080113
Review Stop P
Sequence Number 1
Notes
Date Text
2008-08-14 11:59:11PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A1 FLOOR PLAN IS INDICATING THAT A "PORTABLE
 WATER COOLER TO BE PRESENT PRIOR TO FINAL INSPECTION".
 A PORTABLE WATER COOLER DOES NOT MEET THE FBC-2004
 PLUMBING TABLE 403.1 MINIMUM NUMBER OF REQUIRED
 PLUMBING FIXTURES FOR A BUSSINESS OCCUPANCY. A DRINKING
 FOUNTAIN IS REQUIRED PER TABLE 403.1. PLEASE KNOW THAT
 BOTTLED WATER DISPENSERS (PORTABLE WATER COOLERS) SHALL
 BE PERMITTED TO BE SUBSTITUTED FOR NOT MORE THAN 50
 PERCENT OF THE REQUIRED DRINKING FOUNTAINS. PLEASE KNOW
 THIS PORTABLE WATER COOLER IS SUBSTITUTING FOR 100
 PERCENT OF THE REQUIRED DRINKING FOUNTAINS. PLEASE
 COMPLY WITH THE REQUIRED DRINKING FOUNTAIN.
 NOTE: THE REQUIRED DRINKING FOUNTAIN SHALL COMPLY WITH
 THE FOLLOWING FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
  
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
  
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
  
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
  
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE. CLEARLY INDICATE THE CLEAR FLOOR SPACE ON SHEET
 A1 FLOOR PLAN.
  
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 2.CLEARLY INDICATE THE REQUIRED CLEAR FLOOR SPACE
 FOR THE NEW SINK ON SHEET A1, FLOOR PLAN COMPLIANT WITH
 FBC-2004 CHAPTER 11, FLORIDA ACCESSIBLITY CODE SECTION
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 NOTE: THE BATHROOM DOOR SWING IS NOT ALLOWED IN THE
 CLEAR FLOOR SPACE. PER CHAPTER 11, SECTION 11-4.22.2.
  
 3. SHEET P-1 SANITARY WASTE PLAN AND SANITARY WASTE
 ISOMETRIC: CLEARLY INDICATE THAT THE 2" WASTE FOR THE
 NEW SINK WILL DISCHARGE DOWNSTREAM OF THE WET VENTED
 EXISTING BATHROOM. PER FBC-2004 PLUMBING SECTION 909.1
 WET VENT PERMITTED.
  
 4. SHEET P-1 DOMESTIC WATER PLAN AND DOMESTIC WATER
 ISOMETRIC: PLEASE KNOW THAT A WATER-HAMMER ARRESTOR IS
 REQUIRED FOR THE COLD WATER SUPPLY TO THE REFRIGERATOR.
 PER FBC-2004 PLUMBING SECTION 604.9 WATER-HAMMER. A
 WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE QUICK
 CLOSING VALVES ARE UTILIZED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]