| 2008-08-13 13:40:36 | |
| | ** DENIED PLANS.** |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN |
| | THE FOLLOWING MINIMUM CODES. |
| | FBC 2004 W/ 2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ( PLANS STATE 2002 NFPA-70) THIS CODE HAS NOT BEEN IN |
| | EFFECT IN THE STATE OF FLORIDA SINCE DEC 8TH2006 |
| | |
| | 2) NOTE: PLEASE INCLUDE MINIMUM LEVELS FOR ANY NEW |
| | HORN/STROBE DEVICES PER FBC 11-4.28.1,.2 AND .3 (4) FOR |
| | ADA. |
| | |
| | 3) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | FOR AUTOMATED LIGHTING CONTROLS REQUIRED. PLANS SHOW A |
| | SWITCH AT FRONT AND REAR OF SPACE WHICH IS NOT |
| | ACCEPTABLE. |
| | PLEASE BE SURE TO SEE THE SECTIONS AS NOTED FOR |
| | SEPARATE SPACES AS WELL AS BREAK ROOMS. |
| | |
| | 4) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| | |
| | 5) NOTE: PANEL SCHEDULE INDICATES A 2-POLE CIRCUIT FOR |
| | EXISTING SIGNAGE HOWEVER NO SIGN CIRCUIT(S) IS SHOWN ON |
| | PLANS AT THE LOCATION REQUIRED PER 600.5. |
| | |
| | 6) NOTE: PLEASE SEE NOTES FOR COLOR CODING OF |
| | CONDUCTORS. THE 277/480V SYSTEMS ARE NOTED FOR BROWN, |
| | ORANGE, AND YELLOW.PLEASE KNOW IF ANY THESE SYSTEMS |
| | ARE 277/480V, THE COLOR CODING SHALL BE BROWN, PURPLE, |
| | AND YELLOW. |
| | ** ORANGE IS FOR HIGH-LEG DELTA SYSTEMS> |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |