Plan Review Notes
Plan Review Notes For Permit 08080100
Permit Number 08080100
Review Stop P
Sequence Number 4
Notes
Date Text
2008-12-15 16:53:04REVISION DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
 FBC-2004 PLUMBING
  
 1. SHT P0.1 THE SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. THE CLEANOUT AND THE FUTURE CAPPED
 STUBOUT NEAR THE TURN INDICATED ON THE FLOOR PLAN ARE
 NOT SHOWN ON THE SANITARY RISER DIAGRAM. PLEASE
 CORRELATE. SECTIONS 106.1.1, 701.1 & 708 AS WELL AS
 TABLE 710.1(2).
  
 2. SHT P0.1 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE SHUT OFF VALVE SHOWN ON THE FUTURE LINE
 ON THE FLOOR PLAN IS NOT INDICATED ON THE WATER RISER
 DIAGRAM. PLEASE CORRELATE. SECTIONS 106.1.1 & 601.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  