| Plan Review Notes For Permit 08080100 |
| Permit Number |
08080100 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-09-05 13:40:27 | ***DENIED*** | | | | | | 1) REQUIRED 2A-10B,C RATED FIRE EXTINGUISHERS TO BE | | | MOUNTED AT LOCATIONS NOT TO EXCEED 75' TRAVEL DISTANCE. | | | SEE OPEN SPACE 108. | | | | | | 2) FIRE DAMPERS TO BE TESTED FOR CLOSURE IN ACCORDANCE | | | WITH UL 555 PRIOR TO FINAL INSPECTION. | | | | | | 3) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHEET | | | FA0.1, NOTE 17 | | | | | | 4) PLEASE PROVIDE EXCEPTION/APPROVAL TO ALLOW | | | AUDIBLE/VISUAL DEVICE CEILING MOUNTED EQUIPMENT. SHEET | | | FA0.1, NOTES 10 AND 11. (TYPICAL REQUIREMENT) | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|