Plan Review Notes
Plan Review Notes For Permit 08080100
Permit Number 08080100
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-09-05 13:40:27***DENIED***
  
 1) REQUIRED 2A-10B,C RATED FIRE EXTINGUISHERS TO BE
 MOUNTED AT LOCATIONS NOT TO EXCEED 75' TRAVEL DISTANCE.
 SEE OPEN SPACE 108.
  
 2) FIRE DAMPERS TO BE TESTED FOR CLOSURE IN ACCORDANCE
 WITH UL 555 PRIOR TO FINAL INSPECTION.
  
 3) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHEET
 FA0.1, NOTE 17
  
 4) PLEASE PROVIDE EXCEPTION/APPROVAL TO ALLOW
 AUDIBLE/VISUAL DEVICE CEILING MOUNTED EQUIPMENT. SHEET
 FA0.1, NOTES 10 AND 11. (TYPICAL REQUIREMENT)
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW