| Plan Review Notes For Permit 08080076 |
| Permit Number |
08080076 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-08-28 17:06:54 | *****DENIED***** | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 4. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW | | | WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 5. SHOW THE LOCATION OF THE EXITS, EXIT LIGHTS, | | | EMERGENCY LIGHTS, AND FIRE EXTINGUISHER(S) FOR THE NEW | | | FLOOR PLAN. | | | | | | 6. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS AND | | | FIRE ALARM DEVICES FOR THE NEW FLOOR PLAN. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | |
|