Plan Review Notes
Plan Review Notes For Permit 08080076
Permit Number 08080076
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-28 08:12:26 
  
  
  
  
 **DENIED**
  
  
  
 1) NOTE: NO ELECTRICAL LIGHTING PLAN SUBMITTED. NEED TO
 SHOW ALL LIGHTING, AND HOW LIGHTING IS BEING
 CONTROLLED.
 PLEASE ALSO INDICATE THE LIGHTING PERFORMANCE LEVELS.
 13-415.1.ABC.1.1, .1.2.
 13-415.2, 13-415.2.ABC.1.1,.1.2
 FBC 106.1.1, 106.3.5.1.2 FOR CLARITY AND ADDITIONAL
 INFORMATION TO BE ON PLANS.
  
 2) NOTE: PLEASE COMPLETE PANEL SCHEDULE WITH MINIMUM
 SIZE CONDUCTORS AND OVER CURRENT PROTECTION.
 408.4, 310.16, 240.4
  
 3) NOTE: PLEASE COMPLETE ALL CIRCUITS 15/20AMP 120V IN
 AREAS TO BE GFI OR GFI PROTECTED PER 210.8B2
  
 4) NOTE: PLEASE BE SURE THE PLANS STATE THE MINIMUM
 CODES AS FOLLOWS.
 2004 FBC W2007 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 5) NOTE: PLEASE CONFIRM ANY ADDITIONAL OR RELOCATED
 HORN OR STROBE DEVICES MEETING FBC 11-4.28 FOR ADA.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  