| 2008-08-07 10:33:59 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. |
| | |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE ATTACHED |
| | SAMPLE. OR PROVIDE ANY OTHER FORMAT THAT WILL INCLUDE |
| | ALL REQUIRED INFORMATION TO VERIFY COMPLIANCE WITH THE |
| | PROPOSED INSTALLATION AND PRODUCT APPROVAL |
| | LIMITATIONS. |
| | ***NOTE: YOU MAY USE OPENING DESIGN PRESSURES SHOWN ON |
| | ATTACHED INSTALLATION SCHEDULE OR YOU MAY PROVIDE |
| | ACTUAL DESIGN PRESSURES FOR EACH OPENING. KEEP IN MIND |
| | THAT PROPERTY IS LOCATED IN EXPOSURE "C" WHEN |
| | CALCULATING THE DESIGN PRESSURES. |
| | |
| | 2- CLEARLY CIRCLE ON SHUTTER DRAWINGS SPECIFIC MOUNTING |
| | CONDITIONS (EG; WALL MOUNTED, BUILT OUT, ETC) AND |
| | SPECIFIC ANCHOR TYPE AND SPACING TO BE USED ACCORDING |
| | TO THE DESIGN PRESSURES, EDGE DISTANCE, PANEL SPAN, |
| | CONNECTION TYPE AND STRUCTURE TO BE ATTACHED TO ( |
| | CONCRETE, CONCRETE BLOCK OR WOOD). |
| | |
| | 3- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION |
| | IS TOO LOW. SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | PERMIT VALUATION TO INCLUDE ALL LABOR AND MATERIALS. |
| | OTHERWISE VALUATION WILL BE ESTIMATED USING THE |
| | MARSHALL AND SWIFT ESTIMATING BOOK. |
| | |
| | 4- NOTICE OF COMMENCEMENT MAY BE REQUIRED ONCE UPDATE |
| | PERMIT VALUATION IS PERFORMED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |