Plan Review Notes
Plan Review Notes For Permit 08080065
Permit Number 08080065
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-08-22 10:54:15***DENIED***
  
 1) PLEASE ADD 2003 EDITION TO NFPA 101 UNDER GENERAL
 NOTES.
  
 2) SMOKE DETCTORS ARE SHOWN THAT WOULD IMPLY A DEVICE
 TIED INTO A FIRE ALARM SYSTEM. IF DEVICES ARE SINGLE OR
 MULTIPLE STATION DEVICES THAT RESPOND TO SMOKE AND
 NOTIFY OCCUPANTS, CHANGE REFERENCE TO SMOKE ALARM ON
 PLANS.
  
 3) AC DIFFUSERS IF RELOCATED SHALL BE A MINIMUM OF
 THREE (3) FEET FROM SMOKE ALARMS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW