| 2008-08-22 08:02:42 | BUILDING PLAN REVIEW |
| | PERMIT: 08080065 |
| | ADD: 529 S. FLAGLER DR. #264 |
| | CONT: DESIGN CONTRACTING INC, |
| | TEL: (561)514-2004 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. THE LEVEL OF ALTERATION SHALL BE STATED ON |
| | THE PLANS. |
| | |
| | 5) PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN TO |
| | SHOW EXACTLY WHERE ALL CHANGES WILL OCCUR THROUGH OUT |
| | THE SPACE. IT APPEARS THAT THERE WILL BE NEW SOFFITS |
| | CONSTRUCTED IN VARIOUS ROOMS; PLEASE INDICATE THE |
| | FASTENERS ATTACHMENT AND SPACING FOR THE TOP METAL |
| | TRACK. DOES THE MARBLE FLOOR EXIST OR A NEW ONE WILL BE |
| | INSTALLED? IF THIS IS A NEW FLOOR SYSTEM, PLEASE TAKE |
| | NOTE THAT FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING |
| | UNITS OR BETWEEN A SWELLING UNIT AND PUBLIC OR SERVICE |
| | AREA WITH IN THE STRUCTURE SHALL HAVE AND IMPACT |
| | INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 |
| | IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 492. FBC 1207.3. PROVIDE THE MANUFACTURE SPECIFICATIONS |
| | FOR THE CORK. |
| | |
| | 6) INDICATE ON THE PLANS THE USE AND OCCUPANCY OF THE |
| | BUILDING AND THE TYPE OF BUILDING PER CHAPTER 3 AND 6 |
| | RESPECTIVELY. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |