Plan Review Notes
Plan Review Notes For Permit 08080050
Permit Number 08080050
Review Stop B
Sequence Number 1
Notes
Date Text
2008-08-22 09:11:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ASCE VERSION IS ILLEGIBLE.
  
 2.PLANS STATE THAT THE METAL ROOF SYSTEM IS "BY
 OTHERS" BUT APPLICATION REQUESTS FOR THIS TO BE A PART
 OF THIS PERMIT.PROVIDE A STRUCTURAL DETAIL FOR THE
 METAL ROOF SYSTEM, ROOF FRAMING PLAN, ALL CONNECTIONS,
 FBC R301, OR REMOVE THE "SCREEN" FROM THE SCOPE OF WORK
 ON THE PERMIT APPLICATION (WILL BE PROVISO ITEM;
 SEPARATE PERMIT REQUIRED).
  
 3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FOR THE METAL ROOF PANEL, FAC9B72.PRODUCT APPROVALS
 TO BE REVIEWED BY DESIGNER OF RECORD FBC*106.3.3.
  