| Plan Review Notes For Permit 08080043 |
| Permit Number |
08080043 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-08-04 11:52:00 | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} INDICATE WHAT CALCULATION WAS USED TO DETERMINE THE | | | DEMAND OF 80% USED IN THE CALCULATION GIVEN. | | | | | | 2} THE SERVICE ENTRANCE CONDUCTORS MUST BE SIZED PER | | | 310.15(B)(6) AS THEY ARE IN CONDUIT., OR 310.16, 310.17 | | | DOES NOT APPLY TO FPL SERVICE DROPS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|