Plan Review Notes
Plan Review Notes For Permit 08080031
Permit Number 08080031
Review Stop E
Sequence Number 2
Notes
Date Text
2008-10-30 11:30:39 
  
  
  
 ** DENIED 2ND REVIEW**
  
  
 ** THERE ARE SOME NOTES FROM PREVIOUS REVIEW WHICH ARE
 STILL IN NEED OF BEING ADDRESSED.
 ** SPOKE TO TOM FROM HENZ ENGINEERING AND HE IS AWARE
 OF COMMENTS BELOW. PLANS ARE COMING BACK FOR COMMENTS
 FROM OTHER TRADES PLEASE ADDRESS AT THIS TIME.
  
  
  
  
 1) NOTE: PLEASE PROVIDE LIGHTING DENSITIES PER
 13-415.2, 13-415.2.ABC.1.1, .1.2
  
 2) NOTE: PLEASE PROVIDE CONTROLS FOR NON-24HR LIGHTING
 PER 13-415.1.ABC.1.1, .1.2.
  
 3) NOTE: PLEASE INDICATE MAIN AS DISCUSSED OVER THE
 PHONE AHEAD OF 600AMP METER.
 230.2E.
  
 4) NOTE: PLEASE MAKE NOTE FOR EQUIPMENT GROUNDING PATH
 ON THE LOAD SIDE OF MAIN. AS THE PLANS ARE INDICATING
 RMC, THEN THE CONTRACTOR MUST USED NEW LISTED FITTINGS
 FOR EQUIPMENT GROUNDING.
 PLACE NOTE ON PLANS FOR WORDS TO THAT AFFECT.
 250.122,250.110,250.24.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  