2008-10-22 13:00:03BUILDING PLAN REVIEW
 PERMIT: 08080031
 ADD: 225 CLEMATIS ST.
 CONT: PLAZA CONSTRUCTION
 TEL: (561) 271-5297
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 WED. OCT.22, 08
 2ND REVIEW
 ACTION: DENIED
  
 1A-C) COMPLIED.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) COMPLIED.
  
 2) PLEASE NOTE THIS IS A CONTINUATION OF A FOUR STORY
 BUILDING WHICH IS REGULATED BY FL S S 553.71(7)
 REQUIRING SPECIAL INSPECTION BY THRESHOLD INSPECTORS
 AND THRESHOLD INSPECTION PLAN.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) COMPLIED
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT KEN CONRAD MANAGER OF
 THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR
 FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 2C) COMPLIED.
  
 3) COMPLIED.
  
 4BUILDING PROVISO: WILL NEED MANUFACTURES SPEC FOR
 LIFT. SHEET A2.2 INDICATES A NEW STAIR WAY NEXT TO THE
 ELEVATOR LOBBY. THE EXISTING BUILDING CODE 606.1 A
 BUILDING OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.11-4.1.6(1) (B) AND 11-4.1.6 (2) (A) (II) BOTH
 INDICATE THAT THE LOWER OFFICE LEVEL NEEDS TO BE ON AN
 ACCESSIBLE ROUTE.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7)COMPLIED.
 NEW COMMENT:
 8) DEALS WITH THE ENERGY CALCULATIONS PROVIDED,
 SUBMITTED WAS METHOD "A" THE WHOLE BUILDING METHOD,
 NOTE THE AREA INDICATES 463 SQ FT. THIS IS NOT THE
 WHOLE 4 STORY BUILDING. METHOD C OR JUST THE
 PRESCRIPTIVE METHOD IS ALL THAT WOULD BE NEEDED. PLEASE
 REVIEW 13-400.0 C PRESCRIPTIVE ENVELOPE METHOD.
 A) NOTE ROOF CALCULATION SUBMITTED IS FOR A METAL
 BUILDING WITH BATT INSULATION PLEASE CORRECT.
 B) DOORS INDICATES DOOR FOR THE WEST WALL BUT NOT THE
 DOOR BEING REPLACED ON THE SOUTH WALL.
 C) FLOORS -ARE INDICATED AS ON THE 1ST FLOOR WITH 1 FT
 OF SOIL,AND CARPET AND PADDING BUT WORK IS ALSO BEING
 DONE ON THE SECOND FLOOR
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved