| 2008-10-22 13:00:03 | BUILDING PLAN REVIEW |
| | PERMIT: 08080031 |
| | ADD: 225 CLEMATIS ST. |
| | CONT: PLAZA CONSTRUCTION |
| | TEL: (561) 271-5297 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | WED. OCT.22, 08 |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1A-C) COMPLIED. |
| | |
| | 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E) COMPLIED. |
| | |
| | 2) PLEASE NOTE THIS IS A CONTINUATION OF A FOUR STORY |
| | BUILDING WHICH IS REGULATED BY FL S S 553.71(7) |
| | REQUIRING SPECIAL INSPECTION BY THRESHOLD INSPECTORS |
| | AND THRESHOLD INSPECTION PLAN. |
| | |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) COMPLIED |
| | |
| | 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. CONTACT KEN CONRAD MANAGER OF |
| | THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR |
| | FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 2C) COMPLIED. |
| | |
| | 3) COMPLIED. |
| | |
| | 4BUILDING PROVISO: WILL NEED MANUFACTURES SPEC FOR |
| | LIFT. SHEET A2.2 INDICATES A NEW STAIR WAY NEXT TO THE |
| | ELEVATOR LOBBY. THE EXISTING BUILDING CODE 606.1 A |
| | BUILDING OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH |
| | CHAPTER 11 OF THE FLORIDA BUILDING CODE, |
| | BUILDING.11-4.1.6(1) (B) AND 11-4.1.6 (2) (A) (II) BOTH |
| | INDICATE THAT THE LOWER OFFICE LEVEL NEEDS TO BE ON AN |
| | ACCESSIBLE ROUTE. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) COMPLIED. |
| | |
| | 7)COMPLIED. |
| | NEW COMMENT: |
| | 8) DEALS WITH THE ENERGY CALCULATIONS PROVIDED, |
| | SUBMITTED WAS METHOD "A" THE WHOLE BUILDING METHOD, |
| | NOTE THE AREA INDICATES 463 SQ FT. THIS IS NOT THE |
| | WHOLE 4 STORY BUILDING. METHOD C OR JUST THE |
| | PRESCRIPTIVE METHOD IS ALL THAT WOULD BE NEEDED. PLEASE |
| | REVIEW 13-400.0 C PRESCRIPTIVE ENVELOPE METHOD. |
| | A) NOTE ROOF CALCULATION SUBMITTED IS FOR A METAL |
| | BUILDING WITH BATT INSULATION PLEASE CORRECT. |
| | B) DOORS INDICATES DOOR FOR THE WEST WALL BUT NOT THE |
| | DOOR BEING REPLACED ON THE SOUTH WALL. |
| | C) FLOORS -ARE INDICATED AS ON THE 1ST FLOOR WITH 1 FT |
| | OF SOIL,AND CARPET AND PADDING BUT WORK IS ALSO BEING |
| | DONE ON THE SECOND FLOOR |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |