| Date |
Text |
| 2008-08-07 12:30:22 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A-3.1 SHOW COMPLIANCE FOR THE FOLLOWING: |
| | ___FOR W/C'S |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT |
| | C. 11-4.16.5 FLUSH CONTROLS |
| | ___FOR LAVS |
| | A. 11-4.16.2 CLEARANCES |
| | B. 11-4.16.3 CLEAR FLOOR SPACE |
| | (LAV SHALL BE A MINIMUM 15" OFF THE WALL TO BE CENTERED |
| | ON THE 30" WIDTH OF THE CLEAR FLOOR SPACE. PLEASE |
| | INDICATE ON PLANS). |
| | ___FOR TOILET ROOM |
| | A. 11-4.22..3 TURNING SPACE |
| | |
| | 2. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED FOR |
| | THE BUSINESS OCCUPANCE. PLEASE INDICATE THE LOCATION OF |
| | THE REQUIRED D.F. |
| | |
| | 3. ALL MECHANICAL, ELECTRICAL & PLUMBING SHEETS. THE |
| | CERTIFICATE OF AUTHROIZATION IS REQUIRED IN THE TITLE |
| | BLOCK OF EACH SHEET.--THE ADDRESS IN THE TITLE |
| | BLOCK DOES NOT REFLECT THE ADDRESS OF RECORD IN THE |
| | STATE OF FLORIDA DBPR WEBSITE. (SEE ATTACHED SHEET). |
| | PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR WEBSITE |
| | PRIOR TO RESUBMITTING TO THE CITY WPB FOR REVIEW. FAC |
| | 61G14-23.002(2) & FS 471.025. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |