2008-08-12 14:02:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE PRODUCT APPROVALS FOR A/C CONDENSER STANDS NEED
 TO BE REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL
 APPROVAL (A SHOP REVIEW STAMP AND SIGNATURE WILL MEET
 THIS REQUIREMENT). SEE W.P.B. AMEND. 106.3.
  
 2) SEE PLUMBING REVIEW NOTE #3 REGARDING THE
 ENGINEERING BUSINESS HENZ.. PLEASE CORRECT PER FAC
 61G15-23.002 (2).
  
 3) PLEASE SHOW ON PLAN A-3.1 DETAIL 02, WHAT THE
 R-VALUE FOR THE INSULATION IS IN THE WALL. AS THIS WALL
 MAY BE CONSIDERED AN ADJACENT WALL BECAUSE THE FUTURE
 OFFICE IS NOT OCCUPIED AND THE A/C MAY NOT BE RUNNING
 AT THIS TIME. SEE 2004 FBC 13-402.1.C.1 THEN
 13-402.2.AB.1 AND .2. ( ENERGY CODE FORM 400C-04 SHOWS
 R-13 WOULD BE REQUIRED. ) PLEASE FEEL FREE TO RESPOND
 WITH ANY OTHER INFORMATION FOUND.
  
 MECHANICAL PLAN REVIEW BY;