| Plan Review Notes For Permit 08080031 |
| Permit Number |
08080031 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-08-12 14:02:04 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) THE PRODUCT APPROVALS FOR A/C CONDENSER STANDS NEED | | | TO BE REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL | | | APPROVAL (A SHOP REVIEW STAMP AND SIGNATURE WILL MEET | | | THIS REQUIREMENT). SEE W.P.B. AMEND. 106.3. | | | | | | 2) SEE PLUMBING REVIEW NOTE #3 REGARDING THE | | | ENGINEERING BUSINESS HENZ.. PLEASE CORRECT PER FAC | | | 61G15-23.002 (2). | | | | | | 3) PLEASE SHOW ON PLAN A-3.1 DETAIL 02, WHAT THE | | | R-VALUE FOR THE INSULATION IS IN THE WALL. AS THIS WALL | | | MAY BE CONSIDERED AN ADJACENT WALL BECAUSE THE FUTURE | | | OFFICE IS NOT OCCUPIED AND THE A/C MAY NOT BE RUNNING | | | AT THIS TIME. SEE 2004 FBC 13-402.1.C.1 THEN | | | 13-402.2.AB.1 AND .2. ( ENERGY CODE FORM 400C-04 SHOWS | | | R-13 WOULD BE REQUIRED. ) PLEASE FEEL FREE TO RESPOND | | | WITH ANY OTHER INFORMATION FOUND. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|