Plan Review Notes
Plan Review Notes For Permit 08080031
Permit Number 08080031
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-09-04 15:43:39***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH THE REQUIREMENTS OF NFPA 241.
  
 3) ELEVATOR SHALL COMPLY WITH ASME/ANSI A17.1.
  
 4) SITE SHALL BE CLEANED DAILY OR MORE FREQUENT AS
 NECESSARY TO PREVENT THE BUILD UP OF CONSTRUCTION
 RELATED DEBRIS.
  
 5) CORRECT NFPA REFERENCE ON HARDWARE SCHEDULE; SHEET
 A-2.1 TO NFPA 101, SEC. 7.2.1.5.
  
 6) PLEASE VERIFY IF SCOPE OF WORK INVOLVES (2) HOUR
 RATED WALL ASSEMBLIES. THE DOOR SCHEDULE DOES NOT
 INDICATE (1 1/2 ) HOUR RATED DOORS.
  
 7) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENT FOR WALLS
 AND CEILING.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756