Plan Review Notes For Permit 08080031
Permit Number 08080031
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-13 13:19:12** DENIED PLANS.**
  
  
 1) NOTE: PLEASE SEE 620.23 AS THE LIGHTING IN THE
 ELEVATOR EQUIPMENT ROOM IS REQUIRED TO BE ON A
 DEDICATED CIRCUIT. PLANS SHOW THE LIGHTING BEING
 CIRCUITED TO HALLWAY LIGHTING WHICH IS NOT PERMITTED.
  
 2) NOTE: PLEASE SEE NFPA-101 7.8.1.3 AS THE EGRESS
 LIGHTING IN CORRIDOR NEED TO MEET CONTROLS PER
 7.8.1.2.2 AND FBC 1006.1.2
 THESE DEVICES SHALL BE FAIL SAFE ON.
  
 3) NOTE: PLEASE SEE 700.16 AS BATTERY BACK UP LIGHTING
 OF SOME KIND IS REQUIRED IN THE ELEVATOR EQUIPMENT
 ROOM.
  
 4) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2
 AND SUBMIT LIGHTING PERFORMANCE CALCULATIONS FOR NEW
 AREAS.
 PLEASE SUBMIT A COMPLETED FIXTURE SCHEDULE SHOWING EACH
 FIXTURE TYPE, WATTAGE, MANUFACTURE ETC.
  
 5) NOTE: AS NOTED ABOVE PLEASE SEE 13-415.1.ABC.1.1,
 .1.2 FOR REQUIRED AUTOMATED LIGHTING CONTROLS FOR NEW
 DEVICES. SEE NOTE #2 ABOVE WITH RESPECT TO DEVICES SUCH
 AS OCCUPANCY SENSORS.
  
 6) NOTE: PLEASE SHOW THE LIGHTING LEVELS FOR EGRESS
 UNDER BOTH CONDITIONS OF NORMAL AND EMERGENCY.
 NFPA-101 7.8.1.3, 7.9.2.1, .2.2
  
 7) NOTE:PLEASE SEE FBC 11-4.28.1, .2 AND .3 FOR ADA
 REQUIREMENTS OF HORNS, STROBE ETC.
 PLANS MUST SHOW LOCATIONSAND MINIMUM LEVELS OF
 DEVICES.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  