| 2008-08-13 13:19:12 | ** DENIED PLANS.** |
| | |
| | |
| | 1) NOTE: PLEASE SEE 620.23 AS THE LIGHTING IN THE |
| | ELEVATOR EQUIPMENT ROOM IS REQUIRED TO BE ON A |
| | DEDICATED CIRCUIT. PLANS SHOW THE LIGHTING BEING |
| | CIRCUITED TO HALLWAY LIGHTING WHICH IS NOT PERMITTED. |
| | |
| | 2) NOTE: PLEASE SEE NFPA-101 7.8.1.3 AS THE EGRESS |
| | LIGHTING IN CORRIDOR NEED TO MEET CONTROLS PER |
| | 7.8.1.2.2 AND FBC 1006.1.2 |
| | THESE DEVICES SHALL BE FAIL SAFE ON. |
| | |
| | 3) NOTE: PLEASE SEE 700.16 AS BATTERY BACK UP LIGHTING |
| | OF SOME KIND IS REQUIRED IN THE ELEVATOR EQUIPMENT |
| | ROOM. |
| | |
| | 4) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 |
| | AND SUBMIT LIGHTING PERFORMANCE CALCULATIONS FOR NEW |
| | AREAS. |
| | PLEASE SUBMIT A COMPLETED FIXTURE SCHEDULE SHOWING EACH |
| | FIXTURE TYPE, WATTAGE, MANUFACTURE ETC. |
| | |
| | 5) NOTE: AS NOTED ABOVE PLEASE SEE 13-415.1.ABC.1.1, |
| | .1.2 FOR REQUIRED AUTOMATED LIGHTING CONTROLS FOR NEW |
| | DEVICES. SEE NOTE #2 ABOVE WITH RESPECT TO DEVICES SUCH |
| | AS OCCUPANCY SENSORS. |
| | |
| | 6) NOTE: PLEASE SHOW THE LIGHTING LEVELS FOR EGRESS |
| | UNDER BOTH CONDITIONS OF NORMAL AND EMERGENCY. |
| | NFPA-101 7.8.1.3, 7.9.2.1, .2.2 |
| | |
| | 7) NOTE:PLEASE SEE FBC 11-4.28.1, .2 AND .3 FOR ADA |
| | REQUIREMENTS OF HORNS, STROBE ETC. |
| | PLANS MUST SHOW LOCATIONSAND MINIMUM LEVELS OF |
| | DEVICES. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |