Plan Review Notes
Plan Review Notes For Permit 08080031
Permit Number 08080031
Review Stop B
Sequence Number 1
Notes
Date Text
2008-08-14 09:46:44BUILDING PLAN REVIEW
 PERMIT: 08080031
 ADD: 225 CLEMATIS ST.
 CONT: PLAZA CONSTRUCTION
 TEL: (561) 271-5297
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 14,2008
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) PLEASE NOTE THIS IS A CONTINUATION OF A FOUR STORY
 BUILDING WHICH IS REGULATED BY FL S S 553.71(7)
 REQUIRING SPECIAL INSPECTION BY THRESHOLD INSPECTORS
 AND THRESHOLD INSPECTION PLAN.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT KEN CONRAD MANAGER OF
 THE SPECIAL INSPECTOR PROGRAM AT (561)805-6666 FOR
 FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 2C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 3) DISCREPANCY, SHEET S-1 INDICATES AT THE CENTER
 BOTTOM OF THE SHEET A FIRST FLOOR FOUNDATION PLAN WITH
 DOUBLE DOORS, A-2.1 DOES NOT INDICATE DOUBLE DOORS BUT
 A NEW SINGLE DOOR IN THE FULL FLOOR PLAN, ENTRY STAIR
 AND ENCLOSURE IN DETAIL ARE COVERED UNDER PERMIT #
 07120350 223 CLEMATIS ST CAN NOT BE PART OF THIS
 PERMIT. PERMIT# 07120350 CONTRACTOR IS CASTLE
 FLORIDA.
  
 4) SHEET A2.2 INDICATES A NEW STAIR WAY NEXT TO THE
 ELEVATOR LOBBY. THE EXISTING BUILDING CODE 606.1 A
 BUILDING OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING.11-4.1.6(1) (B) AND 11-4.1.6 (2) (A) (II) BOTH
 INDICATE THAT THE LOWER OFFICE LEVEL NEEDS TO BE ON AN
 ACCESSIBLE ROUTE. THE IMPROVEMENTS TO THE ELEVATOR CAN
 NOT BE USED AS PART OF THE DISPROPORTIONATE COST OF THE
 PROJECT. I'VE SPOKEN WITH THE BUILDING OFFICIAL ON THIS
 MATTER AND THESTATE MAY PROVIDE A WAIVER, THE FORMS FOR
 WAIVER FROM THE STATE ARE ON LINE UNDER
 WWW.FLORIDABUILDING .ORG, CLICK ON FLORIDA BUILDING
 CODE, CLICK ON CHAPTER 11, AT THE BACK OF THE CHAPTER
 IS WHERE THE APPLICATION FOR WAIVER IS LOCATED.
  
 5) SHEET A2.2 THE BACK CORRIDOR THAT LEADS TO THE
 VERTICAL EXIT IS MISSING THE EGRESS DOOR FROM THE
 NIGHTCLUB TO THE EAST. ADDITIONAL INFORMATION REQUIRED
 106.1.2.
  
 6) SHEET A-2.2 DETAIL PARTITION LEGEND WALL TYPE # 7
 INDICATES A WP 7095 BUT THE TI-1.1 DOES NOT PROVIDE THE
 ASSEMBLY AS OTHER WALL ASSEMBLIES ARE PROVIDE. PLEASE
 PROVIDE THE WP 7095 ASSEMBLY INFORMATION. 707.4 &
 707.5.
  
 7) SHEET A-2.2 JUST EAST OF THE NEW RESTROOM
 THEREAPPEARS TO BE ANOTHER SHAFT BUT THE SHAFT WALL
 DESIGNATION IS NOT PROVIDED. 707.4 & 707.5.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.