| Date |
Text |
| 2008-08-01 16:57:44 | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | 1. NOTE: PERMIT APPLICATION STATES THE FOLLOWING |
| | "INSTALL GAS PIPING PER APPROVED PLANS". PLEASE KNOW |
| | THAT THE SUBMITTED PLANS ARE NOT APPROVED FOR THE GAS |
| | PIPING AND THAT A RESIDENTIAL GENERATOR PERMIT IS |
| | REQUIRED FOR THE PROPOSED EMERGENCY GENERATOR. PLEASE |
| | KNOW THAT THIS WAS EXPLAINED IN MISC. PERMIT |
| | APPLICATION #08060901 FOR THE NEW GENERATOR ENCLOSURE |
| | BY MYSELF AND OTHER PLAN REVIEWERS. PLEASE KNOW THAT |
| | THE FOLLOWING IS REQUIRED FOR THE RESIDENTIAL GENERATOR |
| | APPLICATION. |
| | |
| | ******IMPORTANT INFORMATION****** |
| | AS OF 8/25/06 GENERATOR (GEN/RES AND |
| | GEN/COM) PERMIT APPLICATIONS SHALL NOT |
| | BE ACCEPTED UNLESS THE ELECTRICAL INFOR- |
| | MATION AND GAS (OR DIESEL) INFORMATION |
| | IS ALL SUBMITTED AT THE SAME TIME. THE |
| | GENERATOR, ELECTRICAL AND GAS/DIESEL IN- |
| | FORMATION WILL BE ROUTED TOGETHER. THIS |
| | WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY |
| | THE MANUFACTURER'S SPECI- |
| | FICATIONS AND INSTALLATION INSTRUCTIONS) |
| | ARE AVAILABLE TO ALL PLAN REVIEWERS. |
| | |
| | A GAS PERMIT CAN NOT BE ISSUED UNTIL |
| | A GEN/RES PERMIT APPLICATION HAS BEEN |
| | APPLIED FOR AND APPROVED BY ZONING FOR |
| | THE GENERATORS LOCATION. |
| | NOTE: PLEASE KNOW AS OF THE TIME OF THIS PLAN REVIEW A |
| | RESIDENTIAL GENERATOR PERMIT APPLICATION HAS NOT BEEN |
| | SUBMITTED FOR SAID ADDRESS. PLEASE REFERENCE THE PERMIT |
| | INFORMATION OF SAID ADDRESS INDICATING THIS. |
| | |
| | 2. INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT |
| | SEE FAC 61G1-16.004 TITLE BLOCK. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" |
| | SEE CITY WPB AMEND. 106.1.1). |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | NOTE: (4)(5) ARE MISSING FROM THE TITLE BLOCK. |
| | |
| | 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE SECTION 401.1 SCOPE. |
| | NOTE: SUBMITTED PLANS DO NOT HAVE AN ISOMETRIC THAT |
| | SHOWS ALL CUT SECTIONS OF PIPE WITH CORRESPONDING |
| | LENGTHS AS REQUIRED. |
| | |
| | 4. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE. |
| | NOTE: THE ISOMETRIC NEEDS TO CLEARLY INDICATE THE |
| | PIPING MATERIAL BEING USED AND ALL PIPE SIZES FOR EACH |
| | FOR EACH CUT SECTION OF PIPE. |
| | |
| | 5. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL) |
| | ON THE GAS ISOMETRIC. PER FBC-2004 FUEL GAS SECTION |
| | 401.1 SCOPE. |
| | |
| | 6. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: PLANS ARE INDICATING AN "EXIST NATURAL GAS METER |
| | & PRESSURE REGULATOR". PLEASE INDICATE THE EXISTING BTU |
| | LOAD AS WELL AS THE PROPOSED GENERATOR BTU LOAD ON THE |
| | REQUIRED GAS ISOMETRIC. |
| | |
| | 7. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: PLEASE INDICATE THE EXISTING GAS SYSTEMS LONGEST |
| | LENGTH (SEE COMMENT #6 INDICATING AN EXISTING GAS |
| | METER). |
| | |
| | 8. CLEARLY INDICATE THE DELIVERY PRESSURE (PSI) ON THE |
| | REQUIRED GAS ISOMETRIC. PER FBC-2004 FUEL GAS CODE SEC. |
| | 402.2. NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE: TWO COPIES OF MANUFACTURE SHEETS FOR THE |
| | PROPOSED GENERATOR ARE REQUIRED THAT CLEARLY INDICATE |
| | THE GENERATORS MAKE, MODEL NUMBER, BTU LOAD CAPACITY, |
| | AND A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY (TESTING LAB EXAMPLES ARE= AGA, CSA, UL). |
| | PLEASE KNOW THAT THE SUBMITTED SENSUS #143 MP REGULATOR |
| | MANUFACTURER'S SPECIFICATION SHEETS DO NOT INDICATE A |
| | LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. PLEASE COMPLY ON THE RESUBMITTAL THAT THE |
| | MP REGULATOR HAS A LISTING. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |