2008-09-19 15:43:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1. OK
  
 2. SEE OPENING 2. C2 CONNECTION TYPE INTO CONCRETE
 BLOCK REQUIRES 11" SPACING, BUT THE INSTALLATION
 SCHEDULE SPECIFIES 12". PLEASE REVISE AND CHECK ALL.
  
 3RD REVIEW, C1 ALSO REQUIRES 11 INCH SPACING FOR BLOCK
 SUBSTRATE, OPENING 2. PLEASE REVISE AND CHECK ALL. SEE
 ALSO OPENING 1. THIS COMMENT MAY APPLY TO OTHER
 CONNECTIONS/OPENINGS.
  
 NEW COMMENT:
  
 3. PLEASE CORRELATE THE INSTALLATION SCHEDULE WITH THE
 FLOOR PLAN.
  
 4. SHOW THE EMERGENCY MEANS OF ESCAPE ON THE FLOOR PLAN
 FBC R310.4.
  