| Plan Review Notes For Permit 08070871 |
| Permit Number |
08070871 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-08-28 08:54:19 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.SEE OPENING 1.C2 CONNECTION TYPE, TAPCON | | | FASTENER, INTO CONCRETE BLOCK NOT PERMITTED IN SPANS | | | OVER 5' (SEE THAT THERE ARE HATCHED LINES IN THAT BOX, | | | SHEET 4 OF PRODUCT APPROVAL).PLEASE REVISE.THIS | | | COMMENT MAY APPLY TO OTHER OPENINGS. | | | | | | 2.SEE OPENING 2.C2 CONNECTION TYPE INTO CONCRETE | | | BLOCK REQUIRES 11" SPACING, BUT THE INSTALLATION | | | SCHEDULE SPECIFIES 12".PLEASE REVISE AND CHECK ALL. | | | | | | 3.PLEASE PROVIDE TWO COMPLETE COLLATED SETS OF PERMIT | | | DOCUMENTS.OLD SHEETS ARE TO BE SUBMITTED FOR | | | REFERENCE, BUT PULLED OUT OF THE BOUND PERMIT PACKAGE | | | AND VOIDED. |
|