Plan Review Notes
Plan Review Notes For Permit 08070866
Permit Number 08070866
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-28 08:54:18 
 **DENIED**
  
  
  
 1) NOTE: SCOPE OF WORK ON PERMIT APPLICATION CLEARLY
 STATES TO * INSTALL AND UPGRADE OF FIRE ALARM SYSTEM.
 HOWEVER BASED ON THE PLANS SUBMITTED THE PLANS ARE
 INCOMPLETE SHOWING MINIMUM CODE COMPLIANCE.
 PLANS DO NOT INDICATE ANY HEIGHTS OF DEVICES.NFPA-72,
 FBC CHAPTER 9
 PLANS DO NOT INDICATE ANY SCALE WHICH IS REQUIRED. FBC
 106.1.3 ADMINISTRATIVE SECTION
 PLANS DO NOT INDICATE ANY MINIMUM LEVELS FOR DEVICES
 MEETING FBC FOR ADA. 11-4.28.1,.2 AND .3.
 PLANS DO NOT INDICATE DIMENSIONS, OR SUFFICIENT
 INFORMATION AND CLARITY TO DO A REVIEW FOR MINIMUM CODE
 COMPLIANCE. FBC 106.1.1,106.1.2 FOR ADDITIONAL
 INFORMATION
 PLANS DO NOT INDICATE ANY DEDICATED CIRCUIT AS REQUIRED
 FOR FIRE ALARM PANEL PER NFPA-72 4.4.1.4.1 DEDICATED
 BRANCH CIRCUIT. A DEDICATED BRANCH CIRCUIT OF ONE OF
 THE FOLLOWING SHALL SUPPLY PRIMARY POWER:
 (1)COMMERCIAL LIGHT AND POWER.
 (2)AN ENGINE-DRIVEN GENERATOR OR EQUIVALENT IN
 ACCORDANCE WITH4.4.1.9.2, WHERE A PERSON SPECIFICALLY
 TRAINED IN ITS OPERATION IS ON DUTY AT ALL TIMES.
 (3)AN ENGINE-DRIVEN GENERATOR OR EQUIVALENT
 ARRANGED FOR COGENERATION WITH COMMERCIAL LIGHT AND
 POWER IN ACCORDANCE WITH4.4.1.9.2, WHERE A PERSON
 SPECIFICALLY TRAINED IN ITS OPERATION IS ON DUTY AT ALL
 TIMES.
 PLANS DO NOT INDICATE ANY CODES IN WHICH ANY DESIGN WAS
 ATTEMPTED.
  
 2) NOTE: PLANS ARE SIGNED, DATED AND SEALED BY AN
 ENGINEER AS STATED ON THE TITLE BLOCK AS BEING CIVIL,
 STRUCTURAL AND ARCHITECTURAL. PLEASE SEE THE FOLLOWING
 SECTION WHICH HAS BEEN TAKEN DIRECTLY FROM THE FLORIDA
 STATUTES 471.025 (3)
 (3)NO LICENSEE SHALL AFFIX OR PERMIT TO BE AFFIXED
 HIS OR HER SEAL, NAME, OR DIGITAL SIGNATURE TO ANY
 PLAN, SPECIFICATION, DRAWING, FINAL BID DOCUMENT, OR
 OTHER DOCUMENT THAT DEPICTS WORK WHICH HE OR SHE IS NOT
 LICENSED TO PERFORM OR WHICH IS BEYOND HIS OR HER
 PROFESSION OR SPECIALTY THEREIN.
 3) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 WHICH REQUIRES THE PRINTED NAME AND
 PRINTED LICENSE NUMBEROF THE ENGINEER TO BE ON THE
 TITLE BLOCKS.
  
 4) NOTE: PLEASE KNOW BASED ON THE COMMENTS ABOVE THE
 PLANS AND COPY OF PERMIT APPLICATION IS BEING RETAINED
 BY THIS OFFICE.
  
 5) NOTE: PLEASE KNOW AS THE APPLIED SCOPE OF WORK AND
 WORK ON PLANS IS NOT CLEAR THE APPLIED PERMIT VALUE CAN
 NOT BE VERIFIED PER FBC 108.3
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  