| Plan Review Notes For Permit 08070835 |
| Permit Number |
08070835 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-08-28 14:03:28 | ***DENIED*** | | | | | | 1) SOME SHEETS ARE DIFFICULT TO READ. FBC 106.1.1 | | | REQUIRES CONSTRUCTION DOCUMENTS TO BE OF SUFFICIENT | | | CLARITY TO REVIEW FOR CODE COMPLIANCE AND CONFORMANCE | | | WITH RELEVANT LAWS, ORDINANCES RULES AND REGULATIONS. | | | | | | 2) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | | SAFETY SHALL COMPLY WITH NFPA 101, 2003. | | | | | | 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 4) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | | WALLS AND CEILING. | | | | | | 5) FIRE SPRINKLER SYSTEMS ARE REQUIRED FOR MERCANTILE | | | OCCUPANCIES EXCEEDING 12,000 SQ'. NFPA 101, SEC. | | | 36.3.5.1 (2). PROVIDE FIRE SPRINKLER LAYOUT AS REQUIRED | | | BY FBC. ADDITIONALLY, SEPARATE SHOP DRAWINGS AND PERMIT | | | REQUIRED PRIOR TO SYSTEM INSTALLATION. | | | | | | 6) ADDRESS SHALL BE MINIMUM OF 6" IN HEIGHT, 1" WIDTH | | | AND CONTRASTING WITH BACKGROUND FOR COMMERCIAL | | | BUILDINGS. | | | | | | 7) PROVIDE LOCATION OF REQUIRED 2A-10B,C RATED FIRE | | | EXTINGUISHERS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|