| Plan Review Notes For Permit 08070828 |
| Permit Number |
08070828 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-08-04 15:36:02 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEWSECOND | | | CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- INSTALLATION SCHEDULE CALLS FOR CONCRETE BLOCK AS | | | THE SUBSTRATE. REVISE ANCHOR SPACING AS REQUIRED TO | | | REFLECT THE SPACINGSHOWN ON SHEET 4 OF 4OF STORM | | | SHUTTERS FOR CONCRETE BLOCK INSTALLATION. | | | | | | 2- REVISE ANCHOR TYPE SPECIFIED FOR OPENING #9.PANEL | | | MATE ANCHORS ARE NOT FOR WOOD INSTALLATION. SEE SHEET 4 | | | OF 4. | | | | | | 3-REVISE SHUTTER SPAN FOR OPENING #9. IT CAN'T BE 39 | | | X 12.SEE OPENING SIZE. | | | | | | 4-REVISE SHUTTER SPANTO REFLECT OPENING SIZE AND | | | EDGE DISTANCE SHOWN ON THE INSTALLATION SCHEDULE. | | | ***NOTE: EDGE DISTANCEDOESN'T INCLUDE STUCCO FINISH | | | OR ANY OTHER WALL FINISH. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|