| Plan Review Notes For Permit 08070828 |
| Permit Number |
08070828 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-31 14:17:14 | RESIDENTIAL R(3) SHUTTERS, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1-PRODUCT APPROVAL FOR SHUTTERS NOA 02-1120.02 | | | SUBMITTED IS EXPIRED. NEED TO PROVIDE CURRENT PRODUCT | | | APPROVAL. ALSO, PLEASE MAKE SURE COMPLETE PRODUCT | | | APPROVAL IS SUBMITTED. INFORMATION SUBMITTEDIS | | | MISSING THE COVER PAGES OF THIS NOA. | | | | | | 2-INSTALLATION SCHEDULE SUBMITTED: | | | A) SPECIFY THE OPENING DESIGN PRESSURES AS REQUIRED | | | BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE. | | | ***NOTE: YOU MAY USE TABLE R301.2(2) FOR REFERENCE. SEE | | | ATTACHED COPY. | | | | | | B) REVISE ANCHOR SPACING AS REQUIRED TO MATCH TYPE | | | OF CONNECTION. SEE SHEET 2 OF 4 FOR TYPE OF MOUNTING | | | (EG: WALL MOUNT)AND CONNECTION TYPE TO BE USEDAND | | | ANCHOR SPACING SCHEDULE ON SHEET 4 OF 4 FOR MAXIMUM | | | SPACING. ACCORDING TO THE CONNECTION TYPE. | | | | | | C) SPECIFY ANCHOR SPACING FOR OPENING #9.ALSO, | | | SHUTTER SPAN CAN'T BE THE SAME SIZE AS THE OPENING. | | | REVISE AS REQUIRED.ALSO, SPECIFY THE EDGE DISTANCE ON | | | THIS INSTALLATION. INFORMATION ON INSTALLATION SCHEDULE | | | IS BLANK. | | | | | | D) REVISE EDGE DISTANCE FOR OPENING #10 AT CONCRETE | | | BLOCK INSTALLATION. | | | | | | E) REVISE SHUTTER SPAN FOR OPENINGS #1 AND #2. TO | | | REFLECT THE 2.5" EDGE DISTANCESHOWN ON THE | | | INSTALLATION SCHEDULE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|