| 2008-07-31 14:04:57 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | 1. THE FOLLOWING INFORMATION IS REQUIRED FOR THE VENT |
| | HEADER PER FBC-2004 PLUMBING SECTION 903.5 VENT |
| | HEADERS. STACK VENTS AND VENT STACKS CONNECTED INTO A |
| | COMMON VENT HEADER AT THE TOP OF THE STACKS AND |
| | EXTENDING TO THE OPEN AIR AT ONE POINT SHALL BE SIZED |
| | IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 916.1 |
| | (TABLE 916.1) . THE NUMBER OF FIXTURE UNITS SHALL BE |
| | THE SUM OF ALL FIXTURE UNITS ON ALL STACKS CONNECTED |
| | THERETO, AND THE DEVELOPED LENGTH SHALL BE THE LONGEST |
| | VENT LENGTH FROM THE INTERSECTION AT THE BASE OF THE |
| | MOST DISTANT STACK TO THE VENT TERMINAL IN THE OPEN |
| | AIR, AS A DIRECT EXTENSION OF ONE STACK. |
| | NOTE: CLEARLY INDICATE THE FIXTURES AND FIXTURE UNITS |
| | FOR EACH STACK ALSO INDICATE THE DEVELOPED LENGTH PER |
| | SECTION 903.5 AND SIZE PER TABLE 916.1. |
| | |
| | 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |