| Plan Review Notes For Permit 08070817 |
| Permit Number |
08070817 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-09-30 15:37:25 | ***DENIED*** | | | | | | 1) PLEASE SEE NEW COMMENT. (1A) | | | | | | 2) WHERE RAMPS ARE PROVIDED, WORK TO COMPLY WITH | | | APPLICABLE BUILDING CODES AND NFPA 101, SEC. 7.2.5. | | | | | | 3) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR | | | HANDRAILS AND GUARDRAILS. | | | | | | 4) ADDRESS REQUIRED ON ALL BUILDINGS THAT SHALL BE | | | MINIMUM 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH | | | BACKGROUND. | | | | | | 5) PLEASE PROVIDED DISTANCE FROM BUILDING TO CLOSEST | | | FIRE HYDRANT. | | | | | | NEW COMMENTS: | | | | | | 1A) SHEET E1 INDICATES MANUEL PULL STATIONS AND HORNS | | | BUT NO VISUAL APPLIANCES. PLEASE ADD TO DRAWINGS AND | | | ELECTRICAL SYMBOLS. | | | | | | 6) EXIT SIGNS APPEAR TO BE COMBINATION TYPE WITH | | | EMERGENCY LIGHTING BUT NOT SHOWN UNDER ELECTRICAL | | | SYMBOLS FOR VERIFICATION. | | | | | | 7) IF A FIRE ALARM SYSTEM IS PART OF THIS PROJECT, | | | PLEASE SHOW ALL EQUIPMENT INCLUDING THE FIRE ALARM | | | CONTROL PANEL. | | | | | | 8) VERIFY THE LOCATIONS OF EMERGENCY LIGHTING | | | FACILITIES ON SHEET E2. | | | | | | 9) OCCUPANT LOAD SIGN WILL BE REQUIRED AT TIME OF FINAL | | | INSPECTION. CONTACT BUREAU OF FIRE PREVENTION AT (561) | | | 804-4724 FOR ASSISTANCE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|