Plan Review Notes
Plan Review Notes For Permit 08070817
Permit Number 08070817
Review Stop E
Sequence Number 2
Notes
Date Text
2008-09-30 11:57:34 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE VERSION OF THE SUBMITTED ENERGY
 CALCULATIONS IS NOT CORRECT. PLEASE SEE 13-400.3.A AS
 THE VERSION ADOPTED BY THE FLORIDA BUILDING CODE IS
 2.5. THE SUBMITTED IS VERSION 3.0. PLEASE KNOW IT IS
 THE UNDERSTANDING OF THIS OFFICE THAT A FREE PATCH IS
 AVAILABLE ON ENERGY GAUGE WEBSITE TO CHANGE TO VERSION
 2.5.
 ** PLEASE ALSO SEE THE COUNT OF FIXTURES IN THE INPUT
 DATA REPORT OF THE SUBMITTED ENERGY CALCULATIONS IS NOT
 POSSIBLE AS EACH TYPE IS SHOWN AS ONE FIXTURE. PLEASE
 SEE THE PLANS HAVE NUMEROUS FIXTURES NOT ONLY ONE IS
 EACH LOCATION/ZONE/SPACE.
 PLEASE BE SURE TO SEE 13-415.2.,13-415.2.ABC.1.1,.1.2
 AND .1.3.
 PLEASE ALSO SEE THE EXTERIOR LIGHTING AS THE SUBMITTED
 INPUT DATA REPORT ONLY INDICATES A TOTAL OF FIVE
 FIXTURES WHICH IS NOT POSSIBLE BASED ON THE PLANS
 SUBMITTED. THE PLANS SHOW A SUBSTANTIALLY HIGHER NUMBER
 OF FIXTURES. THE WATTAGE OF EACH OF THESE FIXTURES IS
 ALSO NOT THE SAME AS SHOWN ON THE IDR. THE IDR SHOWS A
 TOTAL OF 60WATTS, YET THE PLANS INDICATE 100WATT
 FIXTURES.
  
 ** PLEASE BE SURE TO COORDINATE ALL FIXTURE SON PLANS
 WITH THE INPUT DATA REPORT FOR TYPES, WATTAGES, NUMBER
 OF FIXTURES ETC.
 ** PLEASE SEE THE JURISDICTION IS NOT CORRECT. THE
 APPLICATION IS LOCATED IN THE CITY OF WEST PALM BEACH
  
 2) NOTE: IF PLANS HAVE A * STATE APPROVAL* PLEASE BE
 SURE ALL PLANS CONTAIN THE STATE STAMPS. THE ELECTRICAL
 PLANS AS SUBMITTED DO NOT CONTAIN ANY STAMPS FROM ANY
 OF THE LISTED REVIEWERS.
  
 3) NOTE: PLEASE SEE THE PACKAGE DOES INCLUDE ANY
 ELECTRICAL RISER FOR SERVICE TO CONNECTION OF
 ELECTRICAL SERVICE OR EQUIPMENT.
 230.70.230.71.230.72.230.76,230.79, 250.50, 215.5, 545
 ETC
 FBC 106.1.1,106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 4) NOTE: PLEASE SEE PANEL SCHEDULES ARE NOT COMPLETE OR
 SPECIFIC AS REQUIRED PER 408.4 OF THE 2005 NFPA-70.
 PLEASE SEE COMMENTARY UNDER THE NEC SECTION GIVEN AS
 LISTING *LIGHTING* OR *RECEPTACLES* IN LIEU OF SPECIFIC
 ROOMS OR LOCATIONS IS NOT ACCEPTABLE.
  
 5) NOTE: PLEASE SEE FBC 13-413.2.ABC.2.1 AND2.2 FOR
 MISSING NOTES REQUIRED ON PLANS.
  
 6) NOTE: PLEASE SEE FBC 13-413.1.ABC.1.1 AND .1.2 FOR
 MISSING VOLTAGE DROP CALCULATIONS FOR WORST CASE
 SCENARIO.
  
 7) NOTE: PLANS INDICATE SOME SORT OF NOTES FOR HORNS
 AND STROBES HOWEVER THERE IS NOT INDICATION OR SHOWN
 DESIGN MEETING MINIMUM LEVELS AND LOCATIONS FOR FBC
 11-4.28.1,.2 AND .3 FOR ADA COMPLIANCE.
 PLEASE COMPLETE PLANS AND MINIMUM DEVICE LOCATIONS,
 HEIGHTS, AND LEVELS FOR MINIMUM CODE COMPLIANCE.
  
 8) NOTE: AS SOME INFORMATION HAS NOT BEEN SUBMITTED OR
 SHOWN AT THIS TIME THERE MAY VERY WELL BE NEW COMMENTS
 ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS
 TIME. BASED ON PLANS SUBMITTED A REVIEW WAS DONE AS
 PLANS DID NOT CONTAIN STAMPS. IN EITHER CASE PLANS ARE
 STILL REQUIRED TO MEET MINIMUM CODE DESIGN AND
 COMPLIANCE PER FBC AND OTHER ADOPTED CODES PER FS
 553.73.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  