| 2008-09-30 11:57:34 | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THE VERSION OF THE SUBMITTED ENERGY |
| | CALCULATIONS IS NOT CORRECT. PLEASE SEE 13-400.3.A AS |
| | THE VERSION ADOPTED BY THE FLORIDA BUILDING CODE IS |
| | 2.5. THE SUBMITTED IS VERSION 3.0. PLEASE KNOW IT IS |
| | THE UNDERSTANDING OF THIS OFFICE THAT A FREE PATCH IS |
| | AVAILABLE ON ENERGY GAUGE WEBSITE TO CHANGE TO VERSION |
| | 2.5. |
| | ** PLEASE ALSO SEE THE COUNT OF FIXTURES IN THE INPUT |
| | DATA REPORT OF THE SUBMITTED ENERGY CALCULATIONS IS NOT |
| | POSSIBLE AS EACH TYPE IS SHOWN AS ONE FIXTURE. PLEASE |
| | SEE THE PLANS HAVE NUMEROUS FIXTURES NOT ONLY ONE IS |
| | EACH LOCATION/ZONE/SPACE. |
| | PLEASE BE SURE TO SEE 13-415.2.,13-415.2.ABC.1.1,.1.2 |
| | AND .1.3. |
| | PLEASE ALSO SEE THE EXTERIOR LIGHTING AS THE SUBMITTED |
| | INPUT DATA REPORT ONLY INDICATES A TOTAL OF FIVE |
| | FIXTURES WHICH IS NOT POSSIBLE BASED ON THE PLANS |
| | SUBMITTED. THE PLANS SHOW A SUBSTANTIALLY HIGHER NUMBER |
| | OF FIXTURES. THE WATTAGE OF EACH OF THESE FIXTURES IS |
| | ALSO NOT THE SAME AS SHOWN ON THE IDR. THE IDR SHOWS A |
| | TOTAL OF 60WATTS, YET THE PLANS INDICATE 100WATT |
| | FIXTURES. |
| | |
| | ** PLEASE BE SURE TO COORDINATE ALL FIXTURE SON PLANS |
| | WITH THE INPUT DATA REPORT FOR TYPES, WATTAGES, NUMBER |
| | OF FIXTURES ETC. |
| | ** PLEASE SEE THE JURISDICTION IS NOT CORRECT. THE |
| | APPLICATION IS LOCATED IN THE CITY OF WEST PALM BEACH |
| | |
| | 2) NOTE: IF PLANS HAVE A * STATE APPROVAL* PLEASE BE |
| | SURE ALL PLANS CONTAIN THE STATE STAMPS. THE ELECTRICAL |
| | PLANS AS SUBMITTED DO NOT CONTAIN ANY STAMPS FROM ANY |
| | OF THE LISTED REVIEWERS. |
| | |
| | 3) NOTE: PLEASE SEE THE PACKAGE DOES INCLUDE ANY |
| | ELECTRICAL RISER FOR SERVICE TO CONNECTION OF |
| | ELECTRICAL SERVICE OR EQUIPMENT. |
| | 230.70.230.71.230.72.230.76,230.79, 250.50, 215.5, 545 |
| | ETC |
| | FBC 106.1.1,106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| | CLARITY. |
| | |
| | 4) NOTE: PLEASE SEE PANEL SCHEDULES ARE NOT COMPLETE OR |
| | SPECIFIC AS REQUIRED PER 408.4 OF THE 2005 NFPA-70. |
| | PLEASE SEE COMMENTARY UNDER THE NEC SECTION GIVEN AS |
| | LISTING *LIGHTING* OR *RECEPTACLES* IN LIEU OF SPECIFIC |
| | ROOMS OR LOCATIONS IS NOT ACCEPTABLE. |
| | |
| | 5) NOTE: PLEASE SEE FBC 13-413.2.ABC.2.1 AND2.2 FOR |
| | MISSING NOTES REQUIRED ON PLANS. |
| | |
| | 6) NOTE: PLEASE SEE FBC 13-413.1.ABC.1.1 AND .1.2 FOR |
| | MISSING VOLTAGE DROP CALCULATIONS FOR WORST CASE |
| | SCENARIO. |
| | |
| | 7) NOTE: PLANS INDICATE SOME SORT OF NOTES FOR HORNS |
| | AND STROBES HOWEVER THERE IS NOT INDICATION OR SHOWN |
| | DESIGN MEETING MINIMUM LEVELS AND LOCATIONS FOR FBC |
| | 11-4.28.1,.2 AND .3 FOR ADA COMPLIANCE. |
| | PLEASE COMPLETE PLANS AND MINIMUM DEVICE LOCATIONS, |
| | HEIGHTS, AND LEVELS FOR MINIMUM CODE COMPLIANCE. |
| | |
| | 8) NOTE: AS SOME INFORMATION HAS NOT BEEN SUBMITTED OR |
| | SHOWN AT THIS TIME THERE MAY VERY WELL BE NEW COMMENTS |
| | ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS |
| | TIME. BASED ON PLANS SUBMITTED A REVIEW WAS DONE AS |
| | PLANS DID NOT CONTAIN STAMPS. IN EITHER CASE PLANS ARE |
| | STILL REQUIRED TO MEET MINIMUM CODE DESIGN AND |
| | COMPLIANCE PER FBC AND OTHER ADOPTED CODES PER FS |
| | 553.73. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |