Plan Review Notes
Plan Review Notes For Permit 08070817
Permit Number 08070817
Review Stop M
Sequence Number 1
Notes
Date Text
2008-08-21 11:04:35REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THESE PLANS ARE FOR A MODULAR BUILDING. HOWEVER,
 THERE IS NO INDICATION ON PLANS THAT THEY HAVE BEEN
 SUBMITTED UNDER THE DCA MODULAR BUILDING PROGRAM
 ESTABLISHED UNDER F.S. 553. THEREFORE, THESE PLANS MUST
 BE REVIEWED FOR THE REQUIREMENTS OF NEW SITE-BUILT
 CONSTRUCTION IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE.
  
 2. SHOW THE SIZES OF ALL SUPPLY AND RETURN AIR DUCTS AS
 WELL AS THE CFM BEING SUPPLIED OR RETURNED AT EACH
 REGISTER, GRILL OR DIFFUSER. AN AIR DISTRIBUTION SYSTEM
 SHALL BE DESIGNED AND INSTALLED TO SUPPLY THE REQUIRED
 DISTRIBUTION OF AIR IN ACCORDANCE WITH FBCM 603.1. SHOW
 BALANCED RETURN AIR IN ACCORDANCE WITH FBCM 601.4.
  
 3. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL.
 CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL
 BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED
 PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A
 NUISANCE IN ACCORDANCE WITH FBCM 307.2.1.
  
 4. SHOW MEANS OF AUXILIARY OR SECONDARY DRAIN
 PROTECTION. A SECONDARY DRAIN OR AUXILIARY DRAIN PAN
 SHALL BE REQUIRED FOR EACH COOLING OR EVAPORATOR COIL
 WHERE DAMAGE TO ANY BUILDING COMPONENTS WILL OCCUR AS A
 RESULT OF OVERFLOW FROM THE EQUIPMENT DRAIN PAN OR
 STOPPAGE IN THE CONDENSATE DRAIN PIPING IN ACCORDANCE
 WITH FBCM 307.2.3.
  
 5. PROVIDE OUTSIDE AIR CALCULATIONS SHOWING THE
 OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, OUTSIDE AIR
 PROVIDED AND OUTSIDE AIR REQUIRED FOR EACH SPACE OF THE
 BUILDING IN ACCORDANCE WITH FBCM 403.3.
  
 6. PROVIDE A COMPLETE EQUIPMENT SCHEDULE FOR A/C AND
 EXHAUST EQUIPMENT WHICH SHOWS ALL REQUIRED NAMEPLATE
 INFORMATION, ENERGY EFFICIENCY RATING OF THE APPLIANCES
 AND AIR MOVED (IN CFM) IN ACCORDANCE WITH FBCM 301.2,
 301.6, 403.3, 601.4, 603.1.
  
 7. PROVIDE AN AIR BALANCE SCHEDULE SHOWING THE SPACE TO
 BE PRESSURIZED WITH RESPECT TO THE OUTDOORS IN
 ACCORDANCE WITH FBCB 13-409.1.ABC.2
  
 8. SHOW THE SIZE AND LOCATION OF ALL OUTSIDE AIR AND
 EXHAUST OPENINGS IN THE EXTERIOR OF THE BUILDING TO
 DEMONSTRATE COMPLIANCE WITH FBCM 401.5 AND 401.6. A
 SITE PLAN IS ALSO REQUIRED TO DETERMINE COMPLIANCE WITH
 THESE SECTIONS.
  
 9. SHEET MP HAS A HAND-WRITTEN NOTE INDICATING A
 "SCREENED AUTOMATIC LOUVER." WHAT IS THE PURPOSE OF
 THIS LOUVER? HOW AND WHY IS IT AUTOMATED? WHAT TYPE OF
 LOUVER IS BEING USED? LOUVERS ARE CLASSIFIED AS PANEL
 WALLS IN ACCORDANCE WITH FAC RULE 9B-72. PROVIDE
 PRODUCT APPROVAL FOR ALL OUTDOOR LOUVERS IN ACCORDANCE
 WITH THIS RULE AND FBCB SECTION 1609. ALSO, PLANS SHALL
 NOT BE MODIFIED OR AMENDED BY HAND OR BY ANYONE OTHER
 THAN THE DESIGNER OF RECORD IN ACCORDANCE WITH F.S. 471
 AND FAC RULE 61G15.
  
 10. WHAT TYPE OF MATERIALS ARE THE A/C CLOSET LOUVERED
 DOORS CONSTRUCTED? THESE A/C CLOSETS APPEAR TO BE
 DESIGNED TO FUNCTION AS RETURN AIR PLENUMS. MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL
 HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84 PER FBCM 602.2.1.
  
 11. NO INFORMATION COULD BE FOUND ON PLANS REGARDING
 THE INSTALLATION OF THE OUTDOOR CONDENSING UNITS.
 PROVIDE INSTALLATION DETAILS AS WELL AS LOCATIONS ON
 PLANS SHOWING COMPLIANCE WITH FBCM 301.13 FOR WIND
 RESISTANCE, SECTIONS 303, 304 AND 306.
  
 12. IF THE AIR HANDLERS ARE CAPABLE OF PRODUCING MORE
 THAN 2,000 CFM, COMPLIANCE WITH FBCM 606.2 IS REQUIRED.
 SHOW COMPLIANCE BY PROVIDING SMOKE DETECTORS WITH
 AUDIBLE AND VISIBLE NOTIFICATION DEVICES OR PROVIDE
 MANUFACTURER'S SUBMITTAL DATA SHOWING THESE UNITS ARE
 NOT CAPABLE OF PRODUCING MORE THAN 2,000 CFM.
  
 13. THE ENERGY CODE COMPLIANCE FORM SHALL BE SIGNED AND
 SEALED BY THE PREPARER IN ACCORDANCE WITH FBCB
 13-103.1.1 AND FBCB 13-103.2.
  
 14. PAGE 2 OF THE ENERGY CODE COMPLIANCE FORM REQUIRES
 THAT THE INPUT REPORT BE SUBMITTED WITH THE COMPLIANCE
 REPORT. SEE "IMPORTANT NOTE" ON THAT PAGE. NO SUCH
 REPORT WAS PROVIDED. THE ENERGY CALCULATIONS CAN NOT BE
 REVIEWED WITHOUT THE INPUT REPORT AND THEREFORE ARE NOT
 BEING REVIEWED AT THIS TIME.
  
 15. COOLING LOAD CALCULATIONS SHALL BE PROVIDED AND
 APPENDED TO THE ENERGY CODE COMPLIANCE FORM IN
 ACCORDANCE WITH FBCB 13-407.1 ABC.1.
  
 16. NOTE: PLEASE BE AWARE THAT DUE TO THE LARGE AMOUNT
 OF MISSING INFORMATION, THAT A THOROUGH REVIEW OF THE
 PLANS CAN NOT BE PERFORMED AT THIS TIME. NEW COMMENTS
 ARE LIKELY ONCE PLANS ARE RESUBMITTED WITH MORE
 COMPLETE INFORMATION. IT IS NOT POSSIBLE TO MAKE A
 COMPLETE LIST OF ALL MISSING ITEMS AND POSSIBLE CODE
 VIOLATIONS.
  
 17. NOTE: AS THIS PLAN WAS NOT SUBMITTED UNDER THE DCA
 MODULAR BUILDING PROGRAM, THIS MODULAR BUILDING MAY NOT
 BE DELIVERED WITH ANY ELEMENTS OF "CLOSED
 CONSTRUCTION." ALL STRUCTURAL, BUILDING ENVELOPE,
 MECHANICAL, ELECTRICAL AND PLUMBING SYSTEMS AND
 COMPONENTS MUST REMAIN EXPOSED FOR COMPLETE ROUGH
 INSPECTIONS AS REQUIRED IN ACCORDANCE WITH FBCB SECTION
 109. ANY PORTIONS THAT DO NOT COMPLY WITH THE
 REQUIREMENTS OF THE CODE SHALL BE CORRECTED AND SUCH
 PORTION SHALL NOT BE COVERED OR CONCEALED UNTIL
 AUTHORIZED BY THE BUILDING OFFICIAL IN ACCORDANCE WITH
 FBCB 109.6.
  