| Plan Review Notes For Permit 08070817 |
| Permit Number |
08070817 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-08-26 13:59:57 | ***DENIED*** | | | | | | 1) PLANS INDICATE A FIRE ALARM SYSTEM ON SHEET CV AND | | | SHEET EV1 BUT NO EQUIPMENT IS ILLUSTRATED ON DRAWINGS | | | OR UNDER ELECTRICAL SYMBOLS. ADDITIONALLY, SEPARATE | | | SHOP DRAWINGS AND PERMIT REQUIRED PRIOR TO EQUIPMENT | | | INSTALLATION. | | | | | | 2) WHERE RAMPS ARE PROVIDED, WORK TO COMPLY WITH | | | APPLICABLE BUILDING CODES AND NFPA 101, SEC. 7.2.5. | | | | | | 3) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR | | | HANDRAILS AND GUARDRAILS. | | | | | | 4) ADDRESS REQUIRED ON ALL BUILDINGS THAT SHALL BE | | | MINIMUM 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH | | | BACKGROUND. | | | | | | 5) PLEASE PROVIDED DISTANCE FROM BUILDING TO CLOSEST | | | FIRE HYDRANT. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|