Plan Review Notes
Plan Review Notes For Permit 08070817
Permit Number 08070817
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-13 16:19:35 
  
 ** NO STATE APPROVAL OR STAMPS ON PLANS.
  
  
 **DENIED**
  
 1) NOTE: PLEASE SEE COMPLIANCE WITH THE ENERGY CODE IS
 NOT MET. PLEASE SEE THE CERTIFICATION SHEETS IN BOTH
 SETS ARE NOT ORIGINAL. IN FACT THEY DO NOT CONTAIN A
 SIGNATURE, DATE, OR SEAL FROM THE LISTING DESIGN
 PROFESSIONAL AS REQUIRED.
 PLEASE SEE FS 471.025, FAC 61G15-23.002, FBC 13-103.1.
  
 2) NOTE: PLANS SUBMITTED ARE NOT COMPLETE, NO RISER
 DIAGRAM, NO GROUNDING, NO SERVICE ENTRANCE CONDUCTORS,
 NO FEEDERS, NO AIC RATINGS, NO LOAD CALCULATIONS ETC
 230.70,230.71,230.72,215.5,215.3,240.4,310.16,408.4,220
 ETC.
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 ARE INCOMPLETE. PLEASE SEE PAGE TWO WHICH SPECIFICALLY
 STATES THE INPUT DATA REPORT SHALL ACCOMPANY THE
 CALCULATIONS.
 AS THESE ARE NOT COMPLETE AT THIS TIME, NO VERIFICATION
 OF CODE COMPLIANCE CAN BE DONE.
 PLEASE SEE ADDRESS IS NOT COMPLETE.
 PLEASE SEE JURISDICTION IS NOT CORRECT.
 PLEASE SEE INFORMATION FOR MOST OTHER ITEMS ON COVER
 SHEET ARE ALSO NOT COMPLETE.
  
 ** PLEASE BE SURE TO SEE 13-415.2,
 13-415.2.ABC.1.1,.1.2 AND .1.3.
  
 4) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3. NO
 COMPLIANCE FOR ADA DEVICES IS SHOWN ON PLANS.
 BASE PLANS ARE REQUIRED TO SHOW AT LEAST THE MINIMUM
 FOR CODE COMPLIANCE.
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR REQUIRED
 CONTROLS FOR EXTERIOR LIGHTS. STATING *TIMER* ON PLANS
 DOES NOT SHOW MINIMUM.
  
 6) NOTE: PLEASE BE SURE TO COMPLETE ALL CIRCUITING, ALL
 DESIGNATIONS ON PLANS AND COORDINATE WITH PANEL
 SCHEDULES, FIXTURE LEGEND.
 FBC 106.1.1 FOR ADDITIONAL INFORMATION AND CLARITY .
 NEC 2005, FBC 2004W/2007 REVS.
  
 *** AS THERE IS MUCH INFORMATION NOT YET SUBMITTED
 THERE MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]