2008-07-30 14:30:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE HOOD EXHAUST FAN BEING INSTALLED IS 2,175 CFM'S,
 THE BUILDING MAKE UP AND OUTDOOR AIR IS 1,510 CFM'S,
 THIS WOULD PUT THE BUILDING AT A NEGATIVE PRESSURE. PER
 2004 FBC 13-409.1.ABC.2 BUILDING PRESSURES. MECHANICAL
 SYSTEMS SHALL BE DESIGNED TO ASSURE THAT BUILDINGS ARE
 PRESSURIZED WITH RESPECT TO OUTDOORS. PLEASE HAVE THE
 BUILDING PLANS ENGINEER MARTIN WHITELOCKE REVIEW THE
 HOOD INFORMATION AND REVISE MECHANICAL PLAN 1 OF 1 SO
 THE BUILDING WILL NOT BE AT A NEGATIVE PRESSURE.
  