Plan Review Notes
Plan Review Notes For Permit 08070802
Permit Number 08070802
Review Stop E
Sequence Number 5
Notes
Date Text
2009-04-24 15:43:00PLANS ROUTED TO DOUGLAS WISE (BUILDING OFFICIAL) FOR
 PLUMBING REVIEW AT HIS REQUEST.
  
 PLUMBING PLANS SHOULD BE REDLINED FOR THE NEW DUEL FUEL
 GENERATOR, TANK AND GAS LINES TO BE UNDER SEPARATE
 PERMITS. THIS WAS AGREED TO BY PUBLIX CORPORATE
 REPRESENTATIVE, DESIGN TEAM, CONTRACTOR AND PLAN REVIEW
 STAFF BEFORE PLANS WERE RESUBMITTED. THIS WAS GONE OVER
 WITH MR. ROBERT BROWN ALSO.
 ELECTRICAL, ZONING, AND BUILDING ALREADY HAVE PLANS
 REDLINED FOR SEPARATE PERMIT FOR THE LIFE SAFETY
 GENERATOR.
  
  
2009-04-24 15:42:41** REDLINED PLANS/ PROVISO**
  
 STORE 651, 10130 NORTHLAKE BLVD
  
 1) NOTE: THE LOAD CALCULATIONS ON THE EM PANEL STATES A
 DEMAND LOAD WITH A DEMAND FACTOR OF 1.13. IT IS UNCLEAR
 WHERE THE 1.13 FACTOR IS DERIVED. THIS REVIEWER KNOWS
 OF NO CODE SECTIONS IN THE NEC OR ANY OTHER ADOPTED
 CODES WHICH ALLOWS A DEMAND FACTOR OF 1.13.
 THE LOADS AS SHOWN IN THE PANEL *EM* ARE DEFINED AS
 CONTINUOUS LOADS. BASED ON 230.42, 215.3 AND OTHER
 SECTIONS ADOPTED IN THE NEC THESE LOADS NEED TO BE
 SHOWN AT 125%.
 THE PANEL SCHEDULE SHOWS THE LOAD AT 58AMPS. IF THE
 DEMAND OF 125% IS FIGURED THIS WOULD EXCEED THE RATING
 OF THE BREAKER, THE FEEDERS (BASED ON BREAKER) THE ATS
 AND MAIN BREAKER IN PANEL.
 THIS WOULD REQUIRE EQUIPMENT AND OTHER ITEMS NOW SHOWN
 ON PLANS TO BE REVISED/INCREASED.
 A CALLED WAS PLACED TO EDUARDO DE VARONA AND IS AWARE
 OF THE ISSUE.
  
 2) NOTE: ALL CONTINUOUS LOADS 3 OR MORE HOURS NEED TO
 BE SHOWN AND FIGURED AT 125%. 215.3,230.42.
  
 3) NOTE: AS NOTED ABOVE THE LIFE SAFETY GENERATOR WILL
 BE UNDER SEPARATE PERMIT AND PLANS. VALUATION TO BE
 INCREASED TO FOR NEW ELECTRICAL SCOPE OF WORK ALONG
 WITH THE GENERATOR AND OTHER ASSOCIATED WORK. THESE
 VALUES TO BE INCLUDED WITH THE GENERATOR PERMIT
 APPLICATION.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  