| 2009-04-24 15:43:00 | PLANS ROUTED TO DOUGLAS WISE (BUILDING OFFICIAL) FOR |
| | PLUMBING REVIEW AT HIS REQUEST. |
| | |
| | PLUMBING PLANS SHOULD BE REDLINED FOR THE NEW DUEL FUEL |
| | GENERATOR, TANK AND GAS LINES TO BE UNDER SEPARATE |
| | PERMITS. THIS WAS AGREED TO BY PUBLIX CORPORATE |
| | REPRESENTATIVE, DESIGN TEAM, CONTRACTOR AND PLAN REVIEW |
| | STAFF BEFORE PLANS WERE RESUBMITTED. THIS WAS GONE OVER |
| | WITH MR. ROBERT BROWN ALSO. |
| | ELECTRICAL, ZONING, AND BUILDING ALREADY HAVE PLANS |
| | REDLINED FOR SEPARATE PERMIT FOR THE LIFE SAFETY |
| | GENERATOR. |
| | |
| | |
| 2009-04-24 15:42:41 | ** REDLINED PLANS/ PROVISO** |
| | |
| | STORE 651, 10130 NORTHLAKE BLVD |
| | |
| | 1) NOTE: THE LOAD CALCULATIONS ON THE EM PANEL STATES A |
| | DEMAND LOAD WITH A DEMAND FACTOR OF 1.13. IT IS UNCLEAR |
| | WHERE THE 1.13 FACTOR IS DERIVED. THIS REVIEWER KNOWS |
| | OF NO CODE SECTIONS IN THE NEC OR ANY OTHER ADOPTED |
| | CODES WHICH ALLOWS A DEMAND FACTOR OF 1.13. |
| | THE LOADS AS SHOWN IN THE PANEL *EM* ARE DEFINED AS |
| | CONTINUOUS LOADS. BASED ON 230.42, 215.3 AND OTHER |
| | SECTIONS ADOPTED IN THE NEC THESE LOADS NEED TO BE |
| | SHOWN AT 125%. |
| | THE PANEL SCHEDULE SHOWS THE LOAD AT 58AMPS. IF THE |
| | DEMAND OF 125% IS FIGURED THIS WOULD EXCEED THE RATING |
| | OF THE BREAKER, THE FEEDERS (BASED ON BREAKER) THE ATS |
| | AND MAIN BREAKER IN PANEL. |
| | THIS WOULD REQUIRE EQUIPMENT AND OTHER ITEMS NOW SHOWN |
| | ON PLANS TO BE REVISED/INCREASED. |
| | A CALLED WAS PLACED TO EDUARDO DE VARONA AND IS AWARE |
| | OF THE ISSUE. |
| | |
| | 2) NOTE: ALL CONTINUOUS LOADS 3 OR MORE HOURS NEED TO |
| | BE SHOWN AND FIGURED AT 125%. 215.3,230.42. |
| | |
| | 3) NOTE: AS NOTED ABOVE THE LIFE SAFETY GENERATOR WILL |
| | BE UNDER SEPARATE PERMIT AND PLANS. VALUATION TO BE |
| | INCREASED TO FOR NEW ELECTRICAL SCOPE OF WORK ALONG |
| | WITH THE GENERATOR AND OTHER ASSOCIATED WORK. THESE |
| | VALUES TO BE INCLUDED WITH THE GENERATOR PERMIT |
| | APPLICATION. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |