| 2009-04-05 11:10:15 | ** DENIED 4TH REVIEW ** |
| | |
| | ** SEVERAL NEW NOTES BASED ON REVISED PLANS. SOME ITEMS |
| | WHICH WERE REVISED TO ADDRESS PREVIOUS COMMENTS HAVE |
| | NOW CREATED NEW COMMENTS FOR MANY ITEMS WHICH NEED TO |
| | MEET MINIMUM CODES. |
| | |
| | |
| | 1) NOTE: THE PLANS DO NOT SHOW ANY SCALE FOR THE |
| | ELECTRICAL ROOM. PLEASE SEE NFPA-110 |
| | 7.2.2, 7.2.2.1. |
| | AS THE PLANS DO NOT SHOW A SCALE A DETERMINATION FOR |
| | MINIMUM CODE COMPLIANCE ON CLEARANCE CAN NOT BE MADE. |
| | |
| | 2) NOTE: PLEASE ALSO SEE 700.9 2005 NEC. PLEASE SEE |
| | HANDBOOK COMMENTARY WHICH WILL PROVIDE MORE |
| | INFORMATION. BASED ON THE RISER AND PANELS, THERE IS |
| | OPTIONAL STAND-BY, AND POSSIBLY LEGALLY REQUIRED |
| | SYSTEMS IN THE SAME EQUIPMENT. |
| | MOST CERTAINLY SHOWING CIRCUITS SUCH AS LOTTO MACHINE |
| | AND THE FLORAL SCALE CIRCUITS IN PANELS WHICH ARE |
| | SUPPOSE TO BE FOR LIFE SAFETY SYSTEMS CLEARLY DO NOT |
| | MEET MINIMUM CODES. THESE ARE ONLY TWO CIRCUITS NOTED |
| | WHICH ARE NOT PERMITTED TO BE IN THE 700 SYSTEM PANELS. |
| | THERE ARE MANY OTHERS. |
| | THIS IS NOT A NEW CODE. PLEASE KNOW THAT ALL LIFE |
| | SAFETY 700 SYSTEMS ARE REQUIRED TO BE SEPARATE. THIS |
| | HAS BEEN IN MANY CODE CYCLES FOR BACK MORE THAN TWENTY |
| | YEARS. THIS BUILDING WAS BUILT IN 1999. THE CODES AT |
| | THAT TIME REQUIRED SYSTEMS TO BE SEPARATE. |
| | SEE PLANS AS THERE ARE LIFE SAFETY LOADS (700) , 701 |
| | LOADS AND 702 OPTIONAL STAND-BY LOADS. |
| | *** IT IS BEING NOTED BY THIS REVIEWER IN ORDER TO NOT |
| | DELAY PROJECT(S) SUBMITTED THAT A MEETING BE HELD AS |
| | SOON AS POSSIBLE TO GO OVER ALL STORES IN SUBMISSION TO |
| | THE CITY OF WEST PALM BEACH. |
| | ONCE RISER AND ALL ELECTRICAL SYSTEMS ARE CORRECTED, |
| | THE GENERATORS THEMSELVES MAY BE UNDER SEPARATE |
| | PERMITS. THIS MAY BE DISCUSSED IN MORE DETAIL ONCE |
| | CONTACT/MEETING HAS BEEN HELD. |
| | |
| | 3) NOTE: THE FEEDERS TO PANEL EB DO NOT MEET |
| | 310.16,110.14,240.4. SHOWS #10 AWG ON 40AMP BREAKER. |
| | |
| | 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS ON THE PROPOSED GENERATOR, GENERATOR ENCLOSURE, |
| | ATS EQUIPMENT. BASED ON COMMENT #2 ABOVE, THERE MAY BE |
| | MORE THAN ONE. |
| | ENCLOSURES SHALL MEET NFPA-110 7.2.1.1 |
| | NEC 110.3, 700.6, 90.7 ETC |
| | |
| | 5) NOTE: AN EXPLANATION FOR THE 5-MINUTE PROPOSED TIME |
| | AS SHOWN ON RISER NEEDS TO BE PROVIDED. BASED ON THIS |
| | NOTE ON PLANS, THE 700 SYSTEM WILL NOT ENERGIZE LIFE |
| | SAFETY LOADS FOR 5MINS. |
| | THIS DOES NOT MEET NFPA-110, OR NFPA-70 FOR TIMES FOR |
| | LEVEL ONE, TYPE 10, CLASS 2 SYSTEMS OR ANY 701,TYPE 60 |
| | LOADS. |
| | PLEASE SEE NEC 700.6, 700.12, 700.16, 700.17 ETC |
| | |
| | 6) NOTE: PLEASE PROVIDE LOCATION OF DISCONNECT FOR |
| | FEEDERS MEETING 225.31-225.39. IF USING EXCEPTION IN |
| | 700.12B6, 701.11B5, THEN ALL DISCONNECTING MEANS SHALL |
| | BE READILY ACCESSIBLE AND WITHIN SIGHT. BASED ON THE |
| | PLANS THE GENERATOR DOES MEET WITHIN SIGHT HOWEVER AS |
| | NO DISCONNECTING MEANS IS SHOWN NO OTHER CODE |
| | COMPLIANCE CAN BE VERIFIED. THE SHUNT TRIP DOES NOT |
| | MEET 225.38, 225.39. |
| | THE DISCONNECTING MEANS SHALL BE RATED FOR THE LOAD |
| | SERVED. |
| | ** PLEASE BE AWARE THAT ANY BREAKER ON THE GENERATOR |
| | MAY OR MAY NOT MEET READILY ACCESSIBLE. |
| | |
| | 7) NOTE: CONDUCTORS FROM GENERATOR CAN NOT BE VERIFIED |
| | AS NO OVER CURRENT PROTECTION OF INFORMATION ON THE |
| | GENERATOR IS PROVIDED. 445.13, 310.16, 110.14\ |
| | |
| | 8) NOTE: THE LIGHTING CONTROLS IN BOTH RESTROOMS SHALL |
| | BE DUAL TECHNOLOGY. AS SHOWN IF DEVICES ARE MOTION ONLY |
| | AN OCCUPANT COULD BE OUT OF VIEWING AREA. THIS COULD |
| | CREATE A SAFETY ISSUE. |
| | OTHER DEVICES BEING INSTALLED AS NEW FOR LOCATIONS SUCH |
| | AS COOLERS APPEAR TO BE STANDARD SP SWITCHES. THE |
| | LIGHTING IN THESE AREAS ARE EXEMPT FROM LIGHTING |
| | PERFORMANCE CALCULATIONS HOWEVER ANY NEW BEING |
| | INSTALLED MUST MEET 13-415.1, 13-415.1.ABC.1.1, .1.2 |
| | |
| | 9) NOTE: CODES ON PLANS NEED TO INCLUDE NFPA-110 2002. |
| | |
| | 10) NOTE: NEW NOTE, PLUMBING PLANS SHOW NEW LINES FOR |
| | GAS TO NEW LS GENERATOR. PLEASE BE SURE TO SEE 7.9 OF |
| | NFPA-110, MORE SPECIFICALLY 7.9.3.1. *** THIS IS NOTED |
| | FOR INFORMATION, AS THE GAS REVIEW WILL BE DONE BE THE |
| | PLUMBING PLANS EXAMINERS. LIFE SAFETY SYSTEMS ARE UNDER |
| | REVIEW OF FIRE MARSHAL, BUILDING AND ELECTRICAL PLANS |
| | EXAMINERS. |
| | |
| | 11) NOTE: NEW NOTE: WHERE IS THE DISCONNECTING MEANS |
| | FOR TANK-LESS WATER HEATER? 422.31 MAY BE A SNAP SWITCH |
| | TYPE DEVICE WITH NO OCP. |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |