Plan Review Notes
Plan Review Notes For Permit 08070802
Permit Number 08070802
Review Stop E
Sequence Number 2
Notes
Date Text
2008-10-22 13:06:18** DENIED 2ND REVIEW**
  
  
  
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 ALL SHEETS SUBMITTED BUT ONE ARE THE SAME.
  
  
 1) NOTE: PLANS DO NOT SHOW ANY LIGHTING PERFORMANCE
 CALCULATIONS PER FBC 13-415.2,13-415.2.ABC.1.1, .1.2.
 THE RESPONSE LETTER SUBMITTED MAKES NOTE OF COMPLIANCE
 HOWEVER THE PLANS WHICH ARE THE RECORD SET OF DRAWINGS
 ARE REQUIRED TO BE DESIGNED AND SHOW COMPLIANCE WITH
 THE MINIMUM CODE(S). FS 553.73
 PLEASE BE SURE TO SEE ALL LIGHTING SHOWN ON PLANS FOR
 ALL AREAS IN WHICH NEW LIGHTING IS BEING ADDED. IF THE
 EXISTING AMOUNT OF WATTS PER SQUARE FOOT EXCEEDS
 ALLOWANCE NEW LIGHTING MAY NOT SIMPLY BE ADDED. THIS IS
 FOR ALL AREAS IN WHICH NEW LIGHTING IS BEING SHOWN.
 OTHER ALLOWANCES ETC MAY NEED TO BE LOOKED INTO FOR
 DESIGN.
  
 2) NOTE: PLEASE SEE SECTIONS OF THE CODE AS NOTED
 PREVIOUSLY FOR REQUIRED LIGHTING CONTROLS WAS NOT
 ADDRESSED. THE RESPONSE MENTIONS *SWITCHES* ARE AND
 WERE PROVIDED ON PLANS. PLEASE SEE FBC 13-415.1.ABC.1.
 THIS SECTION OF THE CODE REQUIRES AUTOMATED LIGHTING
 CONTROLS FOR ALL BUILDINGS OVER 5K SQ FT. AS THIS
 BUILDING MOST CERTAINLY MEETS THIS DEFINITION CONTROLS
 ARE REQUIRED. THE SUBSEQUENT SECTIONS 13-415.1.ABC.1.1,
 .1.2 AND .1.3 IN THIS SITUATION ALSO APPLY. THIS
 REQUIRES ANY SEPARATE SPACES TO CONTAIN SEPARATE
 CONTROLS. A *STANDARD SWITCH* DOES NOT MEET THESE
 SECTIONS OF THE CODE AS AUTOMATED SHUT OFF OF SOME KIND
 IT REQUIRED. THIS MAY BE DONE BY OCCUPANCY SENSORS, OR
 MANUAL SWITCH WHICH OVER RIDE SOME SORT OF LIGHTING
 CONTROL SYSTEM. THERE ARE LITERALLY DOZENS OF WAYS TO
 ACHIEVE MINIMUM CODE COMPLIANCE. PLEASE ADDRESS THIS
 COMMENT.
 ** THE ENERGY CODE REQUIRES ALL NEW BEING INSTALLED OR
 REPLACED TO MEET PRESCRIPTIVE REQUIREMENTS.
  
 3) NOTE: PLEASE OBTAIN A LETTER FROM PUBLIX CORPORATE
 OFFICES/ LAW DEPARTMENT WHICH NEEDS TO STATE THE STORE
 WILL NOT BE OCCUPIED WHEN THE NORMAL POWER AS WELL AS
 THE OPTIONAL STAND-BY GENERATOR IS LOST AND UNDER LIFE
 SAFETY GENERATOR POWER. (OR WORDS TO THAT AFFECT). THIS
 INCLUDES EMPLOYEES NOT ONLY THE PUBLIC.
  
 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  