| 2008-10-22 13:06:18 | ** DENIED 2ND REVIEW** |
| | |
| | |
| | |
| | |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | ALL SHEETS SUBMITTED BUT ONE ARE THE SAME. |
| | |
| | |
| | 1) NOTE: PLANS DO NOT SHOW ANY LIGHTING PERFORMANCE |
| | CALCULATIONS PER FBC 13-415.2,13-415.2.ABC.1.1, .1.2. |
| | THE RESPONSE LETTER SUBMITTED MAKES NOTE OF COMPLIANCE |
| | HOWEVER THE PLANS WHICH ARE THE RECORD SET OF DRAWINGS |
| | ARE REQUIRED TO BE DESIGNED AND SHOW COMPLIANCE WITH |
| | THE MINIMUM CODE(S). FS 553.73 |
| | PLEASE BE SURE TO SEE ALL LIGHTING SHOWN ON PLANS FOR |
| | ALL AREAS IN WHICH NEW LIGHTING IS BEING ADDED. IF THE |
| | EXISTING AMOUNT OF WATTS PER SQUARE FOOT EXCEEDS |
| | ALLOWANCE NEW LIGHTING MAY NOT SIMPLY BE ADDED. THIS IS |
| | FOR ALL AREAS IN WHICH NEW LIGHTING IS BEING SHOWN. |
| | OTHER ALLOWANCES ETC MAY NEED TO BE LOOKED INTO FOR |
| | DESIGN. |
| | |
| | 2) NOTE: PLEASE SEE SECTIONS OF THE CODE AS NOTED |
| | PREVIOUSLY FOR REQUIRED LIGHTING CONTROLS WAS NOT |
| | ADDRESSED. THE RESPONSE MENTIONS *SWITCHES* ARE AND |
| | WERE PROVIDED ON PLANS. PLEASE SEE FBC 13-415.1.ABC.1. |
| | THIS SECTION OF THE CODE REQUIRES AUTOMATED LIGHTING |
| | CONTROLS FOR ALL BUILDINGS OVER 5K SQ FT. AS THIS |
| | BUILDING MOST CERTAINLY MEETS THIS DEFINITION CONTROLS |
| | ARE REQUIRED. THE SUBSEQUENT SECTIONS 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3 IN THIS SITUATION ALSO APPLY. THIS |
| | REQUIRES ANY SEPARATE SPACES TO CONTAIN SEPARATE |
| | CONTROLS. A *STANDARD SWITCH* DOES NOT MEET THESE |
| | SECTIONS OF THE CODE AS AUTOMATED SHUT OFF OF SOME KIND |
| | IT REQUIRED. THIS MAY BE DONE BY OCCUPANCY SENSORS, OR |
| | MANUAL SWITCH WHICH OVER RIDE SOME SORT OF LIGHTING |
| | CONTROL SYSTEM. THERE ARE LITERALLY DOZENS OF WAYS TO |
| | ACHIEVE MINIMUM CODE COMPLIANCE. PLEASE ADDRESS THIS |
| | COMMENT. |
| | ** THE ENERGY CODE REQUIRES ALL NEW BEING INSTALLED OR |
| | REPLACED TO MEET PRESCRIPTIVE REQUIREMENTS. |
| | |
| | 3) NOTE: PLEASE OBTAIN A LETTER FROM PUBLIX CORPORATE |
| | OFFICES/ LAW DEPARTMENT WHICH NEEDS TO STATE THE STORE |
| | WILL NOT BE OCCUPIED WHEN THE NORMAL POWER AS WELL AS |
| | THE OPTIONAL STAND-BY GENERATOR IS LOST AND UNDER LIFE |
| | SAFETY GENERATOR POWER. (OR WORDS TO THAT AFFECT). THIS |
| | INCLUDES EMPLOYEES NOT ONLY THE PUBLIC. |
| | |
| | 4) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |