| Date |
Text |
| 2009-04-02 19:06:26 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | NFPA-58 |
| | |
| | A. SHT P-4 FIGURE I.1(B) NOTE 1. REGARDLESS OF ITS |
| | SIZE, ANY ASME CONTAINER FILLED ON SITE MUST BE LOCATED |
| | SO THAT THE FILLING CONNECTION AND FIXED MAXIMUM LIQUID |
| | LEVEL GAUGE ARE AT LEAST 10 FT FROM ANY EXTERNAL SOURCE |
| | OF IGNITION. SEE TABLE 6.3.9. TANK IS A MAXIMUM 7 FT TO |
| | THE FAR SIDE OF THE GENERATOR. |
| | |
| | B. SUBMIT THE FOLLOWING INFORMATION FOR THE SEPARATE |
| | GAS PERMIT REQUIRED: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - ALSO SHOW THE AUTOMATIC |
| | TRANSFER VALVE AND SHUT OFF VALES. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | 7. INDICATE THE BTU LOAD OF THE EXISTING GENERATOR THAT |
| | WILL BE REMOVED. |
| | |
| | 8. SUBMIT MANUF. SPECIFICATIONS FOR THE AUTOMATIC |
| | TRANSFER VALVE THAT SWITCHES THE GENERATOR FROM LP GAS |
| | TO NATURAL GAS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |