Notes
Date Text
2009-04-02 19:06:26DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
 NFPA-58
  
 A. SHT P-4 FIGURE I.1(B) NOTE 1. REGARDLESS OF ITS
 SIZE, ANY ASME CONTAINER FILLED ON SITE MUST BE LOCATED
 SO THAT THE FILLING CONNECTION AND FIXED MAXIMUM LIQUID
 LEVEL GAUGE ARE AT LEAST 10 FT FROM ANY EXTERNAL SOURCE
 OF IGNITION. SEE TABLE 6.3.9. TANK IS A MAXIMUM 7 FT TO
 THE FAR SIDE OF THE GENERATOR.
  
 B. SUBMIT THE FOLLOWING INFORMATION FOR THE SEPARATE
 GAS PERMIT REQUIRED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - ALSO SHOW THE AUTOMATIC
 TRANSFER VALVE AND SHUT OFF VALES.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 7. INDICATE THE BTU LOAD OF THE EXISTING GENERATOR THAT
 WILL BE REMOVED.
  
 8. SUBMIT MANUF. SPECIFICATIONS FOR THE AUTOMATIC
 TRANSFER VALVE THAT SWITCHES THE GENERATOR FROM LP GAS
 TO NATURAL GAS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  