| Plan Review Notes For Permit 08070802 |
| Permit Number |
08070802 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-08-29 14:44:52 | ***DENIED*** | | | | | | 1) NOTE SHOULD READ NFPA 101, 2003 UNDER BUILDING CODE | | | ANALYSIS. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 3) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR | | | HANDRAILS AND GUARDRAILS. | | | | | | 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 5) DUCT SMOKE DETCTORS SHALL INITIATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | 6) REQUIRED ILLUMINATED EXIT SIGNS SHALL NOT EXCEED A | | | DISTANCE OF GREATER THAN 100'. | | | | | | 7) PLEASE INDICATE DOORS PROVIDED WITH PANIC OR FIRE | | | EXIT HARDWARE ON DOOR SCHEDULE. | | | | | | 8) PLEASE CLARIFY FIRE ALARM REMODEL. IS THE FIRE ALARM | | | CONTROL PANEL EXISTING OR WILL IT BE CHANGED OUT? | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|