Plan Review Notes
Plan Review Notes For Permit 08070802
Permit Number 08070802
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-08-29 14:44:52***DENIED***
  
 1) NOTE SHOULD READ NFPA 101, 2003 UNDER BUILDING CODE
 ANALYSIS.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 3) PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR
 HANDRAILS AND GUARDRAILS.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 5) DUCT SMOKE DETCTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 6) REQUIRED ILLUMINATED EXIT SIGNS SHALL NOT EXCEED A
 DISTANCE OF GREATER THAN 100'.
  
 7) PLEASE INDICATE DOORS PROVIDED WITH PANIC OR FIRE
 EXIT HARDWARE ON DOOR SCHEDULE.
  
 8) PLEASE CLARIFY FIRE ALARM REMODEL. IS THE FIRE ALARM
 CONTROL PANEL EXISTING OR WILL IT BE CHANGED OUT?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756