| 2008-08-13 15:11:46 | **DENIED** |
| | |
| | 1) NOTE: PLEASE CONFIRM LICENSING OF THE FIRM AS |
| | LISTED. THE CERTIFICATE OF AUTHORIZATION NUMBER SHOWN |
| | IS LISTED FOR POST, BUCKLEY, SCHUH AND JERNIGAN, INC AT |
| | A LOCATION OTHER THAN LISTED ON PLANS. THE FIRM NAME AS |
| | LISTED ALONG WITH ADDRESS IS NOT LISTED ON STATE |
| | WEBSITE. |
| | PLEASE ALSO INDICATE THE ARCHITECTURAL FIRM LICENSE |
| | NUMBER THE NUMBER AS LISTED DOES COME UP ON WEBSITE FOR |
| | ENGINEERING FIRM HOWEVER NOT FOR ARCHITECTURAL |
| | BUSINESS. |
| | PLEASE SEE FS 471.023 (ENG) FS 481.219 (ARCH)AND FAC |
| | 61G15-23.002, 61G1-16.004. |
| | |
| | 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED |
| | ON THE ELECTRICAL PLANS AS WELL AS CORRECTING COVER |
| | SHEETS. |
| | THE LIFE SAFETY PLAN . |
| | |
| | 2004 FBC W/2007 REVISIONS. |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 3) NOTE: PLEASE INDICATE THE REQUIRED BATTERY BACK UP |
| | LIGHTING FOR ALL EGRESS PATHS IN AREAS IN WHICH WORK IS |
| | BEING DONE. AS THIS LOCATION IS A LOCATION IN WHICH |
| | OCCUPANCY WILL OCCUR UNDER GENERATOR POWER IN ANY EVENT |
| | OF POWER FAILURE BATTERY BACK UP LIGHTING FOR 1FT |
| | CANDLE MINIMUM FOR EGRESS PATHS WILL BE REQUIRED. |
| | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.1, .2.2. |
| | |
| | ** NORMAL OCCUPANCY IS BEING PROPOSED IN THIS LOCATION |
| | UNDER EMERGENCY POWER. IN THIS SITUATION LOSING THE |
| | *EMERGENCY* BACK UP WOULD CAUSE ALL EGRESS AREAS TO |
| | HAVE NO LIGHTING WHICH IS A LIFE SAFETY SITUATION. |
| | ** THE BACK UP FOR NORMAL IS CURRENTLY THE EMERGENCY |
| | LIFE SAFETY GENERATOR. BASED ON THIS THE STORE IS |
| | REQUIRED TO BE EVACUATED UNDER EMERGENCY POWER. IF |
| | EMERGENCY POWER IS THE *NORMAL* POWER THERE IS *NO* |
| | BACK UP FOR LIFE SAFETY. |
| | |
| | ** IF EGRESS LIGHTING IS CURRENTLY PROVIDED WITH |
| | BATTERY BACK UP MEETING THE LIFE SAFETY CODE IN ANY |
| | AREAS, PLEASE INDICATE. |
| | AT THIS TIME NO KNOWN BATTERY BACK UP POWER FOR MAIN |
| | AREAS ARE KNOWN TO BE BATTERY BACK UP. |
| | |
| | 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS IN AREAS IN WHICH NEW LIGHTING IS BEING |
| | INSTALLED. |
| | PLEASE SEE13-415.2.ABC.1.1, .1.2. |
| | |
| | 5) NOTE: PLEASE PROVIDE HOW LIGHTING CONTROLS FOR NEW |
| | BEING INSTALLED MEET SECTIONS 13-415.1.ABC.1.1,.1.2 AND |
| | .1.3. |
| | PLEASE BE SURE TO SEE REQUIREMENTS FOR SEPARATE SPACES |
| | AND AREAS SUCH A LOUNGE FOR EMPLOYEES. |
| | |
| | 6) NOTE:ALL CONTINUOUS LOADS SHALL BE SHOWN AT 125%. |
| | 215.3,230.42 ETC |
| | |
| | 7) NOTE: PLEASE SEE RISER AS ALL CONDUCTORS SHALL BE |
| | PROTECTED BY THE OVER CURRENT PROTECTION LIMITING THE |
| | LOAD. 240.4,310.16 ETC |
| | BASED ON RISER, MDP SHOWS A 225AMP BREAKER FEEDING NEW |
| | PANEL *T*. (BASED ON RISER) |
| | |
| | *** THE EXISTING RISER AS SHOWN WAS NOT REVIEWED FOR |
| | CODE COMPLIANCE. |
| | |
| | *** AS THERE IS MUCH INFORMATION NOT YET SUBMITTED |
| | THERE MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |