| 2008-08-13 10:00:03 | BUILDING PLAN REVIEW |
| | PERMIT: 08070802 |
| | ADD: 10130 NORTHLAKE BLVD. |
| | CONT: OAK CONSTRUCTION |
| | TEL: (954)583-9625 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | AUGUST 12, 2008 |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B ) INFORMATIONAL FL S S 713.13 NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 2) PBS & J NO CERTIFICATE OF AUTHORIZATION WAS FOUND |
| | FOR A ARCHITECTS OFFICE, NO CERTIFICATE OF |
| | AUTHORIZATION WAS FOUND FOR PBS & J (DBA) FOR AN |
| | ENGINEERS OFFICE. THERE IS CURRENTLY A CERTIFICATE OF |
| | AUTHORIZATION FOR POST, BUCKLEY, SCHUH & JEERNIGAN, |
| | INC. |
| | 481.219 F.S. CERTIFICATE OF AUTHORIZATION. (ARCHITECTS) |
| | THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN |
| | ARCHITECT PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL |
| | SERVICES, SHALL INCLUDE THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH |
| | SHEET. |
| | THIS MAY BE ADDED BY HAND. |
| | 471.023 F.S. CERTIFICATE OF AUTHORIZATION. (ENGINEER) |
| | THE TITLE BLOCK FOR ANY SHEET BEARING THE NAME OF AN |
| | ENGINEER PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING |
| | SERVICES, SHALL INCLUDE THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET. |
| | THIS MAY BE ADDED BY HAND. |
| | |
| | 3) SHEET D-1 NOTE # 140 INDICATES THE INSTALLATION OF A |
| | NEW OBSEERVATION WINDOW, IS THIS FOR OBSEERVATION ONLY |
| | OR A PICK UP WINDOW AS WELL? PRODUCT APPROVALS ARE |
| | REQUIRED FOR GLAZED OPENINGS. |
| | 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | 3A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, OF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: |
| | 1) OBSERVATION WINDOW OR |
| | 2) PICKUP WINDOW |
| | |
| | 3B) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 3C) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.) |
| | SHEET D-1 NOTE 140 INDICATES A NEW THROUGH THE WALL |
| | OBSERVATION WINDOW, IS THIS A TRUE PICK UP WINDOW? WILL |
| | NEED PRODUCT APPROVAL FOR GLAZED UNIT. |
| | |
| | 4) S-3 DETAILS 1 & 3 DO NOT INDICATE ANY INFORMATION AS |
| | TO WIND DESIGN FOR NEW ROOF TOP A/C UNIT OR NEW |
| | PHARMACY WINDOW. |
| | |
| | 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| | BUILDING: |
| | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| | (KM/HR). |
| | 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3. |
| | WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| | DIRECTION SHALL BE INDICATED. |
| | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| | PROFESSIONAL. |
| | |
| | 5) SHEET S-1 DETAIL 1 & 2 INDICATE NEW FLOOR SECTIONS |
| | BUT THERE IS NO MENTION OF SOIL TREATMENT OF TERMITES. |
| | 1816.1 TERMITE PROTECTION. |
| | TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED |
| | TERMITICIDES, INCLUDING SOIL APPLIED PESTICIDES, |
| | BAITING SYSTEMS, AND PESTICIDES APPLIED TO WOOD, OR |
| | OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED |
| | FOR USE AS A PREVENTATIVE TREATMENT TO NEW |
| | CONSTRUCTION. SEE SECTION 202 , REGISTERED TERMITICIDE. |
| | UPON COMPLETION OF THE APPLICATION OF THE TERMITE |
| | PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL |
| | BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED |
| | PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING |
| | STATEMENT: ?THE BUILDING HAS RECEIVED A COMPLETE |
| | TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. |
| | TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS |
| | ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE |
| | AND CONSUMER SERVICES.? |
| | |
| | 6) SHEET D-1A DEMO NOTE# 35 REMOVAL OF EXISTING |
| | RAILINGS, PLEASE PROVIDE A LOCATION WHERE RAILINGS ARE |
| | TO BE REMOVED, I COULD NOT LOCATE THIS ITEM ON SHEET |
| | D-1? ADDITIONAL INFORMATION REQUIRED 106.1.2. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |