2008-07-30 15:56:05RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OFCOMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- ACCORDION SHUTTERS PRODUCT APPROVAL FL2482 SUBMITTED
 IS FOR THE 2001 BUILDING CODE VERSION.NEED TO PROVIDE
 PRODUCT APPROVAL FOR THE 2004 BUILDING CODE VERSION,
 WHICH IS THE CURRENT CODE IN EFFECT.
  
 3- CLEARLY IDENTIFY SHUTTER MOUNTING CONNECTION TYPE
 (EG: WALL MOUNT, BUILD OUT MOUNT SECTION, ETC.)
 ON COLUMN 4 OF INSTALLATION SCHEDULE TO VERIFY
 COMPLIANCE WITH THE ANCHOR SPACING.
  
 4- CLARIFY/REVISE SIZE OF SHUTTER SPAN. THIS IS A
 WOOD FRAMED HOUSE.ANCHORS NEED TO BE ANCHORED TO THE
 OPENING FRAMING MEMBERS,NOT TO THE PLYWOOD SHEATHING.
 LOOK AT ANCHOR SCHEDULE TABLE FOR WOOD FRAMED OPENINGS.
 SHUTTER SPAN NEEDSTO BE COORDINATED ACCORDING TO THE
 OPENING SIZE AND MINIMUM EDGE DISTANCE REQUIRED.
 REVISE INFORMATION AS REQUIRED.
  
 5- WHAT ARE THE OPENINGS DESIGN PRESSURES. WHAT'S STD
 PER ENG SPEC? SHOWN ON THE WALL PRESSURE COLUMN OF
 INSTALLATION SCHEDULE SUBMITTED.
  
 6- WHAT DOES THE INFORMATION SHOWN ON OPENING NO COLUMN
 STANDS FOR?. EG: WHATDOES3-4-7-8ASTANDS FOR.
 THIS COLUMN IS TO WRITE DOWN THE OPENING NUMBER.
  
 7- CLEARLY MARK ON ACCORDION SHUTTERS DRAWINGS SPECIFIC
 MOUNTING CONDITIONS, AND ANCHOR TYPE AND SPACING TO BE
 USED ACCORDING TO THE DESIGN PRESSURES, PANEL SPAN,
 EDGE DISTANCE, CONNECTION TYPE AND STRUCTURE TO BE
 ATTACHED TO.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712