| 2008-07-30 15:56:05 | RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OFCOMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 2- ACCORDION SHUTTERS PRODUCT APPROVAL FL2482 SUBMITTED |
| | IS FOR THE 2001 BUILDING CODE VERSION.NEED TO PROVIDE |
| | PRODUCT APPROVAL FOR THE 2004 BUILDING CODE VERSION, |
| | WHICH IS THE CURRENT CODE IN EFFECT. |
| | |
| | 3- CLEARLY IDENTIFY SHUTTER MOUNTING CONNECTION TYPE |
| | (EG: WALL MOUNT, BUILD OUT MOUNT SECTION, ETC.) |
| | ON COLUMN 4 OF INSTALLATION SCHEDULE TO VERIFY |
| | COMPLIANCE WITH THE ANCHOR SPACING. |
| | |
| | 4- CLARIFY/REVISE SIZE OF SHUTTER SPAN. THIS IS A |
| | WOOD FRAMED HOUSE.ANCHORS NEED TO BE ANCHORED TO THE |
| | OPENING FRAMING MEMBERS,NOT TO THE PLYWOOD SHEATHING. |
| | LOOK AT ANCHOR SCHEDULE TABLE FOR WOOD FRAMED OPENINGS. |
| | SHUTTER SPAN NEEDSTO BE COORDINATED ACCORDING TO THE |
| | OPENING SIZE AND MINIMUM EDGE DISTANCE REQUIRED. |
| | REVISE INFORMATION AS REQUIRED. |
| | |
| | 5- WHAT ARE THE OPENINGS DESIGN PRESSURES. WHAT'S STD |
| | PER ENG SPEC? SHOWN ON THE WALL PRESSURE COLUMN OF |
| | INSTALLATION SCHEDULE SUBMITTED. |
| | |
| | 6- WHAT DOES THE INFORMATION SHOWN ON OPENING NO COLUMN |
| | STANDS FOR?. EG: WHATDOES3-4-7-8ASTANDS FOR. |
| | THIS COLUMN IS TO WRITE DOWN THE OPENING NUMBER. |
| | |
| | 7- CLEARLY MARK ON ACCORDION SHUTTERS DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS, AND ANCHOR TYPE AND SPACING TO BE |
| | USED ACCORDING TO THE DESIGN PRESSURES, PANEL SPAN, |
| | EDGE DISTANCE, CONNECTION TYPE AND STRUCTURE TO BE |
| | ATTACHED TO. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |